Af-600 fp metasys, 1 start-up of the frequency converter – GE Industrial Solutions AF-600 FP Metasys User Manual

Page 17

Advertising
background image

2.2.1 Start-up of the Frequency Converter

Use the frequency converter keypad mounted either on the drive or remote. Use the Extended Menu key to access the O-## group parameters (Options / Comms).
The settings shown below are typical. Some settings may be changed to meet the application requirements. The settings below will serve as a good starting
reference. Refer to the operating instruction manual for instructions on changing parameters and programming the drive.

Examples of typical settings. Program the following:

Parameter:

Setting:

par. O-30 Protocol

[3] Metasys N2

par. O-31 Address

1 (Default)

par. O-32 Drive Port Baud Rate

[2] 9600 Baud (fixed at 9600 for N2 protocol)

par. O-50 Coasting Select

[3] Logic OR

par. O-52 DC Brake Select

[3] Logic OR

par. O-53 Start Select

[3] Logic OR

par. O-54 Reversing Select

[0] Digital input

par. O-55 Set-up Select

[3] Logic OR

par. O-56 Preset Reference Select

[3] Logic OR

par. O-94 Bus Feedback 1

0

par. O-95 Bus Feedback 2

0

NB!
Send an F command to begin communications between the master and the drive!

Example 1:

F command

Setting:

Device address

XX

Char1 command

F

Checksum

YY

Message code:
>XXFYY <CR>

Issue a run command through the master, to the device:

Example 2:

Network start, BO override command:

Setting:

Device address

XX

Char1 command

7

Char1 subcommand

2

Char2 region

04

Char2 object number (NPA)

04 (Start)

Char2 override value

01 (Active)

Checksum

YY

Message code:
>XX72040401YY <CR>

Issue a frequency reference through the master, to the device:

AF-600 FP Metasys

16