3 Appendix

3.1.1 Analog Inputs (AI)

NPT

NPA

UNIT

DESCRIPTION

RANGE

PAR.NUMBER

AI

0

%

Reference [%]

-

DR-02

AI

1

-

Reference [Unit]

-

DR-01

AI

2

-

Feedback

-

DR-52

AI

3

Hz

Frequency

-

DR-13

AI

4

-

User defined readout

-

DR-09

AI

5

A

Current

-

DR-14

AI

6

kW

Power

-

DR-10

AI

7

hp

Power

-

DR-11

AI

8

V

Output Voltage

-

DR-12

AI

9

V

DC Voltage

-

DR-30

AI

10

%

Motor Thermal Protection

-

DR-18

AI

11

%

Inverter Thermal Protection

-

DR-35

AI

12

V

Terminal 53 analog

-

DR-62

AI

13

V

Terminal 54 analog

-

DR-64

AI

14

Reserved

-

AI

15

Reserved

-

AI

16

%

External reference

-

DR-50

AI

17

C

Heat sink temperature

-

DR-34

AI

18

Hour

Operating hours

-

ID-00

AI

19

Hour

Running hours

-

ID-01

AI

20

kWh

kWh counter

-

ID-02

AI

21

-

Number of Power-ups

-

ID-03

AI

22

-

Number of Over temps

-

ID-04

AI

23

-

Number of Over voltages

-

ID-05

AI

24

Start Ups

ID-08

AI

25

Torque [%]

DR-22

AI

26

Speed [rpm]

DR-17

AI

27

Analog Input, GPIO X30/11

DR-75

AI

28

Analog Input, GPIO X30/12

DR-76

AI

29

Analog Input X42/1

-20.000 to +20.000

LG-30

AI

30

Analog Input, X42/3

-20.000 to +20.000

LG-31

AI

31

Analog Input, X42/5

-20.000 to +20.000

LG-32

AI

40

Bypass Running Hours

0-2

32

/10

BP-11

The default values are shown in bold on the following pages. Any point not listed on the following pages is reserved for future use.

Some Metasys software uses an object number range from 0 to 255, other Metasys software uses the range 1 to 254. The latter software will interpret object
number 0 as 1, and 1 as 2, etc. To access the proper point with this Metasys software, add 1 to the NPA number in the tables.

AF-600 FP Metasys

21

3