Af-600 fp metasys, 4 binary outputs (bo) – GE Industrial Solutions AF-600 FP Metasys User Manual

Page 28

Advertising
background image

3.1.4 Binary Outputs (BO)

NPT

NPA

UNIT

DESCRIPTION

RANGE

1)

PAR. NUMBER

BO

0

-

DC brake inverse

0=Active, 1=Not Ac-

tive

DR-00

BO

1

-

Coast inverse

0=Active, 1=Not Ac-

tive

DR-00

BO

2

-

Stop inverse

0=Active, 1=Not Ac-

tive

DR-00

BO

3

-

Freeze output inverse

0=Active, 1=Not Ac-

tive

DR-00

BO

4

-

Start

0=Not active, 1=Active

DR-00

BO

5

-

Stop

0=Not active, 1=Active

DR-00

BO

6

-

Jog

0=Not active, 1=Active

DR-00

BO

8

-

Relay01

0=Not active, 1=Active

DR-00

BO

9

-

Relay02

0=Not active, 1=Active

DR-00

BO

10

-

Reversing

0=Not active, 1=Ac-

tive0=Not active,

1=Active

DR-00

BO

11

-

Setup LSB

0=Not active, 1=Active

DR-00

BO

12

-

Setup MSB

0=Not active, 1=Active

DR-00

BO

13

-

Preset ref. LSB

0=Not active, 1=Active

DR-00

BO

14

-

Preset ref. MSB

0=Not active, 1=Active

DR-00

BO

20

-

Output Terminal 27

0=Not active, 1=Active

E-90

BO

21

-

Output Terminal 29

0=Not active, 1=Active

E-90

BO

22

-

Output Terminal X30/6 0=Not active, 1=Active

E-90

BO

23

-

Output Terminal X30/7 0=Not active, 1=Active

E-90

BO

24

-

CC Relay 1

0=Not active, 1=Active

E-90

BO

25

-

CC Relay 2

0=Not active, 1=Active

E-90

BO

26

-

Option B Relay 1

0=Not active, 1=Active

E-90

BO

27

-

Option B Relay 2

0=Not active, 1=Active

E-90

BO

28

-

Option B Relay 3

0=Not active, 1=Active

E-90

BO

29

-

Reserved

0=Not active, 1=Active

E-90

BO

30

-

Reserved

0=Not active, 1=Active

E-90

BO

31

-

Reserved

0=Not active, 1=Active

E-90

BO

32

-

Reserved

0=Not active, 1=Active

E-90

BO

33

-

Reserved

0=Not active, 1=Active

E-90

BO

34

-

Reserved

0=Not active, 1=Active

E-90

BO

35

-

Reserved

0=Not active, 1=Active

E-90

BO

36

-

Option C Relay 1

0=Not active, 1=Active

E-90

BO

37

-

Option C Relay 2

0=Not active, 1=Active

E-90

BO

38

-

Option C Relay 3

0=Not active, 1=Active

E-90

BO

39

-

Option C Relay 4

0=Not active, 1=Active

E-90

BO

40

-

Option C Relay 5

0=Not active, 1=Active

E-90

BO

41

-

Option C Relay 6

0=Not active, 1=Active

E-90

BO

42

-

Option C Relay 7

0=Not active, 1=Active

E-90

BO

43

-

Option C Relay 8

0=Not active, 1=Active

E-90

BO

44

-

Reserved

0=Not active, 1=Active

E-90

BO

45

-

Reserved

0=Not active, 1=Active

E-90

BO

46

-

Reserved

0=Not active, 1=Active

E-90

BO

47

-

Reserved

0=Not active, 1=Active

E-90

BO

48

-

Reserved

0=Not active, 1=Active

E-90

BO

49

-

Reserved

0=Not active, 1=Active

E-90

BO

50

-

Reserved

0=Not active, 1=Active

E-90

-

BO

60

-

No Flow Detection

0=Not active, 1=Active

AP-21

BO

61

-

Enable Interval be-

tween starts

Disable, 1=Enable

AP-75

1) The values in BOLD are the default values.