Af-600 fp metasys, 8 analog input commands (not acknowledged) – GE Industrial Solutions AF-600 FP Metasys User Manual

Page 11

Advertising
background image

2.1.8 Analog Input Commands (Not Acknowledged)

DRIVE

Response

Com-

mand

Region

NPA Object no.

Attribu-

te No.

Attribute Message Type

Error
Code

Comments

NAK

1

1

0-23

4

Float

Read Analog Input

11

1 )

Read Linear Ranging Parameter 1

attribute associated with each

individual point. (JCI use only)

NAK

1

1

0-23

5

Float

Read Analog Input

11

1)

Read Linear Ranging Parameter 2

attribute associated with each

individual point. (JCI use only)

NAK

2

-

0-23

2

Byte

Write Analog Input

11

1)

Object Status writeable

NAK

2

-

0-23

3

Float

Write Analog Input

11

1)

Analog Input Value not writeable

NAK

2

-

0-23

4

Float

Write Analog Input

11

1)

Write to Linear Ranging Parameter

1 attribute associated with each

individual point. (JCI use only)

NAK

2

-

0-23

5

Float

Write Analog Input

11

1)

Write to Linear Ranging Parameter

2 attribute associated with each

individual point. (JCI use only)

NAK

2

-

0-23

6

Float

Write Analog Input

11

1)

Write to Linear Ranging Parameter

3 attribute associated with each

individual point. (JCI use only)

NAK

2

-

0-23

7

Float

Write Analog Input

11

1)

Write to Linear Ranging Parameter

4 attribute associated with each

individual point. (JCI use only)

NAK

2

-

0-23

13

Integer Write Analog Input

11

1)

Write to Filter Weight attribute as-

sociated with each individual point.

(JCI use only)

NAK

2

-

0-23

14

Float

Write Analog Input

11

1)

Write to AI Offset attribute associ-

ated with each

individual point. (JCI use only)

1)

Error code 11 is used because attributes are considered as fields/records in the point map database.

Table 2.3: No Subcommand coloumn in this table.