Af-600 fp metasys, 5 internal floating point (adf) – GE Industrial Solutions AF-600 FP Metasys User Manual
Page 29
3.1.5 Internal Floating Point (ADF)
NPT
NPA
UNIT
DESCRIPTION
RANGE
PAR. NUMBER
ADF
0
-
Max valuer of custom readout
Please refer to
K-30
ADF
10
kW
Motor power
P-07
ADF
11
V
Motor voltage
F-05
ADF
12
Hz
Motor frequency
F-04
ADF
13
A
Motor Current(IM.N)
P-03 (mAmp)
ADF
14
RPM
Motor nom. Speed
P-06
ADF
16
%
Resonance damping
H-64
ADF
18
Sec
Start delay
F-24 (mSec!)
ADF
19
%
Preheat DC-current
B-00
ADF
20
%
DC brake current
B-01
ADF
21
Sec
DC braking time
B-02
ADF
22
Hz
DC brake cut-in frequency
B-04
ADF
30
Hz
Output freq. low limit(FMIN)
F-16
ADF
31
Hz
Output freq. high limit(FMAX)
F-03
ADF
32
Unit
Min reference (RefMIN)
F-52
ADF
33
Unit
Max. reference (RefMAX)
F-53
ADF
34
Sec
Accel Time
F-07
ADF
35
Sec
Decel Time
F-08
ADF
36
Hz
Jog Frequency
C-20
ADF
37
%
Digital Reference 1
C-05:0
ADF
38
%
Digital Reference 2
C-05:1
ADF
39
%
Digital Reference 3
C-05:2
ADF
40
%
Digital Reference 4
C-05:3
ADF
41
A
Current Limit
H-71
ADF
42
Hz
Frequency bypass bandwidth
C-01:0
ADF
43
Hz
Frequency 1 Bypass
C-04:0
ADF
44
Hz
Frequency 2 Bypass
C-01:1
ADF
45
Hz
Frequency 3 Bypass
C-04:1
ADF
46
Hz
Frequency 4 Bypass
C-01:2
ADF
47
A
Warning Current Low(ILOW)
C-04:2
ADF
48
A
Warning Current High(IHIGH)
C-01:3
ADF
49
Hz
Warning Freq. Low(FLOW)
C-04:3
AF-600 FP Metasys