2.1.13 Binary Output Commands (Acknowledged)

DRIVE

Response

Command

Subcom-

mand

Region NPA Object no.

Attribute No.

Attribute Message Type

Comments

ACK

1

-

4

0-10

1

Byte

Read Binary Output Read structure attributes associ-

ated with each individual point

ACK

1

-

4

0-10

2

Byte

Read Binary Output Read structure attributes associ-

ated with each individual point

ACK

2

-

4

0-10

1

Byte

Write Binary Output Write to Object Configuration at-

tribute associated with each

individual point

ACK

7

2

4

0-10

-

Byte(0/1) Override Binary Out-

put

Write to binary output current

state (Drive control word)

ACK

7

2

4

0-10

-

Byte(0/1) Override Binary Out-

put

Write to binary output current

state (Drive control word)

ACK

7

3

4

0-10

-

-

Override Release

Set the current value, the value

that it was before the 1. Override

Command was issued

ACK, no action

1

-

4

0-10

3

Integer

Read Binary Output Read Minimum On-time attribute

associated with each

individual point. Return value = 0

ACK, no action

1

-

4

0-10

4

Integer

Read Binary Output Read Minimum Off-time attribute

associated with each

individual point. Return value = 0

ACK, no action

1

-

4

0-10

5

Integer

Read Binary Output Read Maximum Cycles/ Hour at-

tribute associated with each

individual point. Return value = 0

ACK, no action

2

-

4

0-10

3

Integer

Write Binary Output Write Minimum On-time attribute

associated with each individual

point

ACK, no action

2

-

4

0-10

4

Integer

Write Binary Output Write Minimum Off-time attribute

associated with each individual

point

ACK, no action

2

-

4

0-10

5

Integer

Write Binary Output Write Maximum Cycles/ Hour at-

tribute associated with each

individual point

ACK, no action

7

7

4

0-10

-

-

Write Binary Output Optional command for slave de-

vices. Only Attributes used for N2

commissioning purposes

ACK, no action

7

8

4

0-10

-

-

Read Binary Output Optional command for slave de-

vices. Only Attributes used for N2

commissioning purposes

Table 2.7: No Error Code coloumn in this table.

2.1.14 Binary Output (BO) Commands (Not Acknowledged)

DRIVE

Response

Command

Region

NPA Object no.

Attribute No.

Attribute Message Type

Error Code

Comments

NAK

1

4

0-10

6

Integer Read Binary Out-

put

11

1)

Read Interstage on delay attribute

associated with each individual

point. (JCI use only)

NAK

1

4

0-10

7

Integer Read Binary Out-

put

11

1)

Read Interstage off delay attribute

associated with each individual

point. (JCI use only)

NAK

2

4

0-10

2

Byte

Write Binary Out-

put

11

1)

Object Status not writeable

NAK

2

4

0-10

6

Integer Write Binary Out-

put

11

1)

Write Interstage on delay attribute

associated with each individual

point. (JCI use only)

NAK

2

4

0-10

7

Integer Write Binary Out-

put

11

1)

Write Interstage off delay attribute

associated with each individual

point. (JCI use only)

1)

Error code 11 is used because attributes are considered as fields/records in the point map database.

Table 2.8: No Subcommand coloumn in this table.