Af-600 fp metasys, 4 error codes, 5 drive parameters – GE Industrial Solutions AF-600 FP Metasys User Manual

Page 8

Advertising
background image

2.1.4 Error Codes

Error codes

Error Code 00

is issued after power up or after a time out where all overridden points were released, as long as no Identify yourself command
has been issued by the master.

Error Code 01

is issued if the command is not supported or not known by the drive.

Error Code 02

is issued if the received message has a checksum error.

Error Code 03

is issued if the N2 message receive buffer exceeds 256 characters.

Error Code 05

is issued if the received N2 message is too long.

Error Code 10

is issued the data is out of expected range

Error Code 11

is issued when:

1. A point attributes or attribute bit is unused.

2. A point attributes or attribute bit is for JCI use only.

3. An internal data point attribute for current value can not be changed while running

Error Code 12

is issued when:

1. The N2 master tries to change attribute 2 bit 6 "Current State" on a BO and the drive is tripped.

2. The N2 master tries to change attribute 2 bit 6 "Current State" on a BO and the drive is trip locked except for BO 5 "reset"

2.1.5 Drive Parameters

The following parameters may need to be manually set for each drive in the Metasys N2 network. Refer to the Installation, Operation and Maintenance Manual
for the frequency converter for programming.

Parameter list

DRIVEPARAMETER

DESCRIPTION

DEFAULT

DESIRED SETTING

O-01

Control Side

Digital & Ctrl. Word

O-02

Control Source

Drive Port

Drive Port

O-03

Control Word Timeout

60 s

1-18000 s

O-30

Protocol

Drive

Metasys N2

O-31

Address

1

1-255

O-32

Drive Port Baud Rate

9600

Fixed to 9600

O-33

Drive Port Parity

Even, 1stop

Fixed to No Parity, 1stop

O-37

Maximum Inter-char Delay

25 s for Metasys N2

AF-600 FP Metasys

7

2

Advertising