2.2.3 Status Update Request

A Status Update Request will cause the drive to report its current operating status. The status codes, descriptions and associated alarms are shown in the chart
below.

The Device Status Code consists of two parts. The Least Significant Byte, (LSB) of the hex number is the Alarm Number. The Most Significant Byte (MSB) indicates
if the alarm is a normal trip (01) that can be reset automatically or manually, or if the alarm is a trip lock (02) requiring cycling power to the drive.

Status codes with associated alarms and descriptions

Device Status Code1

Alarm No.

Description

0x0000

-

Device OK

0x0102

2

Live zero error

0x0204

4

Phase fault (Trip lock)

0x0107

7

Over voltage

0x0108

8

Under voltage

0x0109

9

Inverter overloaded

0x010A

10

Motor overloaded

0x010B

11

Motor thermistor

0x010C

12

Current limit

0x020D

13

Over current (Trip lock)

0x020E

14

Earth fault (Trip lock)

0x020F

15

Switch mode fault (Trip lock)

0x0210

16

Short circuit (Trip lock)

0x0111

17

Standard bus time out

0x0112

18

HPFB time out

0x0116

22

Auto optimization not OK

0x021D

29

Heat sink temperature to high (Trip lock)

0x011E

30

Motor phase U missing

0x011F

31

Motor phase V missing

0x0120

32

Motor phase W missing

0x0122

34

Profibus communication error

0x0225

37

Inverter fault (Trip lock)

0x013C

60

Safety interlock

0x0263

99

Unknown fault (Trip lock)

Read / Write Notes
A write command to an ADF (Internal Floating Point) or BD (Internal Byte) point type will be stored in the drive's EEPROM.

NB!
If write command is issued to an overridden point, the new value will not be stored in the drive's EEPROM.

AF-600 FP Metasys