4 - location, 5 – installation – GE Industrial Solutions LP11 924 Series 6 & 10 kVA User Manual

Page 13

Advertising
background image

modifications reserved

OPM_LPU_11U_6K0_10K_1US_V010.Doc

12

User manual LP11 924 6 & 10 kVA UPS 1.0


4.4 - LOCATION

• This UPS and Battery Cabinet are intended to be used in a controlled indoor environment and free of conductive

contaminants and protected against animal intrusion.

• Check for sufficient floor loading capacity.

• Avoid placing the unit in direct sunlight or near heat sources.

• It is important that the unit has adequate ventilation. Maintain air movement around and through the unit. Do not

block the air vents.

• The unit must be placed in a sufficiently ventilated area; the ambient temperature for UPS should be in the range of 0

to +40°C (32°F to 104°F). For battery the temperature range should be 20 to 30°C (68°F to 86°F). The battery backup

time will not be optimum outside this temperature range.

• Do not install the UPS in an excessively humid environment or near water.

• Avoid spilling liquids or dropping any foreign object into the UPS.

NOTE

Refer to table 7 for minimum clearance around the UPS for proper ventilation.

4.5 – INSTALLATION

NOTE

The UPS may only be installed by qualified and skilled personnel.

Refer to section 1.3 for further details.

CAUTION

Make sure that condensation does not occur as a result of a relatively low temperature of the unit.

Especially if transport took place at sub-zero temperatures, allow the unit to warm up before installation

and starting up.

• When installing the UPS strictly observe all information on technical data and operating conditions. Comply with all

warnings, and strictly follow the procedures and practices as described in this manual.

• Do not touch electronic components. They may be electrostatic sensitive and are for that reason easily damaged due

to improper handling.

• To avoid potential health risks, electrical components should not be mechanically damaged or destroyed.

NOTE

Before making any connection and switching on the LP11 924 UPS, check the following conditions.

• The voltage and frequency of your utility supply is 120/208/240/277 Vac and 50 or 60 Hz.

• Make sure that the UPS is wired for the present utility voltage. This is indicated on the packaging of the UPS, as well as

at the I/O terminals (11 in Fig.19).

• Make sure that the total power requirement of the equipment to be protected does not exceed the rated output

power of the UPS (output power for your unit is indicated on the rating label on the rear panel).

• When using the 120V split phase outputs make sure that the load per 120V output does not exceed half the rating.

Advertising