1 - installation procedures – GE Industrial Solutions LP11 924 Series 6 & 10 kVA User Manual
Page 15
modifications reserved
OPM_LPU_11U_6K0_10K_1US_V010.Doc
14
User manual LP11 924 6 & 10 kVA UPS 1.0
OUTPUT WIRING:
UPS rating
Output voltage
120V
208V
240V
277V
6 kVA
8 AWG
10 AWG
10 AWG
10 AWG
10 kVA
4 AWG
8 AWG
8 AWG
10 AWG
Table 3. Output wiring
TIGHTENING TORQUE FORCE:
UPS model
Tightening torque force
LP 6-11U
924
18-20 Lbs/inch
LP 6-11U
924
/120V
18-20 Lbs/inch
LP 6-11U
924
/277V
22 Lbs/inch
LP 10-11U
924
22 Lbs/inch
LP 10-11U
924
/120V
18-20 Lbs/inch
LP 10-11U
924
/277V
28 Lbs/inch
Table 4. Tightening torque force
4.5.1 - INSTALLATION PROCEDURES
The LP11 924 UPS is capable of taking four input voltage (120V, 208V, 240V and 277V). The required input voltage should
be mentioned at the time of ordering. According to the order the unit will be equipped with right input voltage. For any
input voltage the UPS can be configured to give any one of the output voltages (120V, 208V, 220V, 230V, 240V, 277V).
Before starting the installation UPS must be fixed to the floor as shown in Fig.6a. Mount the levelers in position A to fix the
UPS to the floor, position B to lift the castors from the floor.
Figure.6a. UPS rear view - Mounting positions for levelers