1 - installation procedures – GE Industrial Solutions LP11 924 Series 6 & 10 kVA User Manual

Page 15

Advertising
background image

modifications reserved

OPM_LPU_11U_6K0_10K_1US_V010.Doc

14

User manual LP11 924 6 & 10 kVA UPS 1.0

OUTPUT WIRING:

UPS rating

Output voltage

120V

208V

240V

277V

6 kVA

8 AWG

10 AWG

10 AWG

10 AWG

10 kVA

4 AWG

8 AWG

8 AWG

10 AWG

Table 3. Output wiring

TIGHTENING TORQUE FORCE:

UPS model

Tightening torque force

LP 6-11U

924

18-20 Lbs/inch

LP 6-11U

924

/120V

18-20 Lbs/inch

LP 6-11U

924

/277V

22 Lbs/inch

LP 10-11U

924

22 Lbs/inch

LP 10-11U

924

/120V

18-20 Lbs/inch

LP 10-11U

924

/277V

28 Lbs/inch

Table 4. Tightening torque force

4.5.1 - INSTALLATION PROCEDURES

The LP11 924 UPS is capable of taking four input voltage (120V, 208V, 240V and 277V). The required input voltage should

be mentioned at the time of ordering. According to the order the unit will be equipped with right input voltage. For any

input voltage the UPS can be configured to give any one of the output voltages (120V, 208V, 220V, 230V, 240V, 277V).

Before starting the installation UPS must be fixed to the floor as shown in Fig.6a. Mount the levelers in position A to fix the

UPS to the floor, position B to lift the castors from the floor.

Figure.6a. UPS rear view - Mounting positions for levelers