GE Industrial Solutions LP11 924 Series 6 & 10 kVA User Manual

Page 52

Advertising
background image

modifications reserved

OPM_LPU_11U_6K0_10K_1US_V010.Doc

51

User manual LP11 924 6 & 10 kVA UPS 1.0

LP11 924 6&10 kVA Weights and Dimensions

Model

Heat dissipation

Linear load

Cabinet Dimensions

Center of gravity

Weight

Altitude

(max 4000m)

100% load

50% load

H

W

D

H

W

D

W

Btu/hr

W

Btu/hr

Inch (mm)

Inch (mm)

Inch (mm)

Inch (mm)

Inch (mm)

Inch (mm)

Lbs (kg)

m

LP 6-11U

924

750

2559

330

1126

26.8 (681)

12.3 (312)

28.7 (729)

11.3 (287)

6.9 (175)

10.4 (264)

197 (89)

<1000, derating

12.5% per 1000

LP 6-11U

924

/120

760

2593

410

1399

39.2 (996)

12.3 (312)

28.7 (729)

11.4 (290)

5.5 (140)

9.1 (231)

355 (161)

LP 6-11U

924

/277

700

2388

321

1096

39.2 (996)

12.3 (312)

28.7 (729)

11.9 (302)

5.6 (142)

8.7 (221)

304 (138)

LP 10-11U

924

1190

4060

550

1876

26.8 (681)

12.3 (312)

28.7 (729)

13.7 (348)

7.1 (180)

10.2 (259)

251 (114)

LP 10-11U

924

/120

1320

4503

620

2115

39.2 (996)

12.3 (312)

28.7 (729)

14.5 (368)

5.5 (140)

10.0 (254)

405 (184)

LP 10-11U

924

/277

1120

3821

535

1826

39.2 (996)

12.3 (312)

28.7 (729)

15.3 (389)

5.4 (137)

9.8 (249)

355 (161)

Table 5. Dimensions

Model

Input wiring

Output wiring

Utility volt. 120V Utility volt. 208V

Utility volt. 240V

Utility volt. 277V Output volt. 120V Output volt. 208V Output volt. 240V Output volt. 277V

AWG/mm

2

AWG/mm

2

AWG/mm

2

AWG/mm

2

AWG/mm

2

AWG/mm

2

AWG/mm

2

AWG/mm

2

LP 6-11U

924

N.A.

8/10

10/6

N.A

N.A.

10/6

10/6

N.A

LP 6-11U

924

/120

4/22

N.A.

N.A.

N.A.

8/10

N.A.

N.A.

N.A.

LP 6-11U

924

/277

N.A.

N.A.

N.A.

10/6

N.A.

N.A.

N.A.

10/6

LP 10-11U

924

N.A.

4/22

6/14

N.A.

N.A.

8/10

8/10

N.A.

LP 10-11U

924

/120

3/27

N.A.

N.A.

N.A.

4/22

N.A.

N.A.

N.A.

LP 10-11U

924

/277

N.A.

N.A.

N.A.

6/14

N.A.

N.A.

N.A.

10/6

Table 6. Wiring details

Model

Minimum free space required

Inches (mm)

Distance between mounting holes

Inches (mm)

Input overcurrent protection

(AMPS)

Output overcurrent protection (AMPS)

Front

Side

Rear

x

y

z

120V

208V

240V

277V

120V

(1 X)

120V

(2X)

208V 240V 277V

LP 6-11U

924

4 (102)

2 (51)

8 (203)

7.24 (184)

22.76 (578)

7.48 (190)

40

35

50

25

30

25

25

LP 6-11U

924

/120

4 (102)

2 (51)

8 (203)

7.24 (184)

22.76 (578)

7.48 (190)

70

50

25

30

25

25

LP 6-11U

924

/277

4 (102)

2 (51)

8 (203)

7.24 (184)

22.76 (578)

7.48 (190)

30

50

25

30

25

20

LP 10-11U

924

4 (102)

2 (51)

8 (203)

7.24 (184)

22.76 (578)

7.48 (190)

70

60

80

40

50

40

35

LP 10-11U

924

/120

4 (102)

2 (51)

8 (203)

7.24 (184)

22.76 (578)

7.48 (190)

120

80

40

50

40

35

LP 10-11U

924

/277

4 (102)

2 (51)

8 (203)

7.24 (184)

22.76 (578)

7.48 (190)

50

80

40

50

40

35

Table 7. Clearance and current limts