5 - transport, storage, 6 - installation – GE Industrial Solutions LP11 924 Series 6 & 10 kVA User Manual

Page 6

Advertising
background image

modifications reserved

OPM_LPU_11U_6K0_10K_1US_V010.Doc

5

User manual LP11 924 6 & 10 kVA UPS 1.0

1.5 - TRANSPORT, STORAGE

• Move the UPS in an upright position and in its original package to the final destination room.

• To lift the UPS, use a forklift or lifting belts with spreader bars.

• Check for sufficient floor and elevator loading capacity.

• Immediately after unpacking carefully check the integrity of the UPS equipment. In case you note recognizable

damage, do not connect any voltage to the UPS, do not put the UPS into operation, but contact the nearest Service

Centre.

• Store the UPS with its batteries fully charged in a dry location, storage temperature must be within -20 and +45°C (-

4°F and 113°F)

• If the unit is stored for an extended period of time, the batteries must be recharged periodically. Connect the unit to

the utility and switch it on:

- if the storage temperature is within -20 and +30°C (-4°F and 86°F), recharge the batteries every 6 months, for 24 hours,

- if the storage temperature is within -20 and +45°C (-4°F and 113°F), recharge the batteries every 4 months, for 24 hours.

1.6 - INSTALLATION

• When installing the UPS strictly observe all information on technical data and operating conditions. Comply with all

warnings, and strictly follow the procedures and practices as described in this manual.

• This UPS is intended to be used in a controlled indoor environment and free of conductive contaminants and

protected against animal intrusion.

• Check for sufficient floor loading capacity.

• Avoid placing the unit in direct sunlight or near heat sources.

• It is important that the unit has adequate ventilation. Maintain air movement around and through the unit. Do not

block the air vents.

• The unit must be placed in a sufficiently ventilated area; the ambient temperature for UPS should be in the range of 0

to +40°C (32°F to 104°F). For battery the temperature range should be 20 to 30°C (68°F to 86°F). The battery backup

time will not be optimum outside this temperature range.

• Do not install the UPS in an excessively humid environment or near water (

95% no condensing)

.

• Avoid spilling liquids or dropping any foreign object into the UPS.

• Do not touch electronic components. They may be electrostatic sensitive and are for that reason easily damaged due

to improper handling.

• To avoid potential health risks, electrical components should not be mechanically damaged or destroyed.

NOTE

Refer to table 7 for minimum clearance around the UPS for proper ventilation.