5 - OPERATION

5.1 - DESCRIPTION OF FRONT AND REAR PANEL

1

LCD screen

2x16 characters, shows UPS system data, status messages, settings.

The language is selectable: English, German, French, Italian, Spanish.

Section 5.4.4 describes the selection procedure.

2-4 Push-buttons

With the button keypads ‘Down’ (2) and ‘Up’ (4) you can scroll through

the several screens, with keypad 'Enter/Reset' (3) a selection is

confirmed. Keypad activity is accompanied by a short beep. If there is

no keypad activity during 20 seconds the LCD screen will return to the

default screen (except for the service screens, see section 5.4.3).

5

LED 'operation' indicates normal operation.

6

LED ‘alarm’, indicates an alarm situation, accompanied by alarm

message(s) on the display and a sounding buzzer.

See section 5.4.2 for more information.

7

Switch ‘UPS on/off’, turns on/off the complete UPS, including the

automatic bypass!

8

Circuit breaker ‘Utility on/off’, protection fuse for utility input and

battery charger.

9

Circuit breaker ‘Bypass on/off’, fuse to protect the system in case of

severe overload or short circuit in the UPS load.

10 Manual Bypass Switch:

1 = Load on UPS

2 = Load on utility

WARNING

In position 2, if the input line is energized, the output is also

live regardless the position of the circuit breakers ‘utility’

and ‘bypass’

11 Cover plate, behind it:

11a Output terminals

11b Input terminals

12 RS232/Contact Interface Card, with:

12a - RS232 Interface Port (see section 6.1)

- Emergency shutdown (see 4.5.1 and 6.2)

- Battery disconnected, pin 1-2 (can be used for external signaling).

13 Free option slot for plug-in cards:

- Relay Card (see 6.3)

- SNMP Card (see 6.4)

14 Option slot for RPA (Redundant Parallel Architecture) Card.

15 DC socket / connector.

16 Battery fuse holder

17 Conduit box

18 Cable inlet

Figure 19 :

Front and rear panel for 208/240V input

5

6

1

2

4

3

16

7 8 9

10

11

a

17

11

b

18

15

11

14
13
12

12

a

Advertising