1 – output voltage 277vac – GE Industrial Solutions LP11 924 Series 6 & 10 kVA User Manual

Page 20

Advertising
background image

modifications reserved

OPM_LPU_11U_6K0_10K_1US_V010.Doc

19

User manual LP11 924 6 & 10 kVA UPS 1.0

4.5.3 - AVAILABLE OUTPUT VOLTAGES: HARDWARE MODIFICATIONS

The following output voltages are available: 120, 208, 220, 230, 240, 277 Vac. An insertion bridge is placed between

terminals 2 and 3. An extra insertion bridge was delivered with the unit (in a plastic bag) to enable other output voltages.

4.5.3.1 – OUTPUT VOLTAGE 277VAC

The off-factory setting is 277VAC; make sure the following steps are implemented:

1. An insertion bridge is placed between terminals 2 and 3.

2. The output tap is set at 277VAC: Please refer to fig.11 and 11a and check the following.

White wire W is connected to faston 67 (connect) on Printed Circuit Board (PCB) part 1113-C

Brown wire F is connected to faston 65 (park) on PCB part 1113-C

Yellow wire L is connected to faston 66 (park) on PCB part 1113-C

3. Connect the output wires to the terminals 1 (L1) and 4 (L2) and ground wire to terminal 5. Ground connection is

essential! See figure 11b.

4. Return to either section 4.5.1.1 step 5 or section 4.5.1.2 step 5. Pay special attention to step 11 in these sections,

i.e. do not forget to modify the display software as described in section 4.5.4.

Output tap changed to 208 Volt

Output tap changed to 240 Volt

Output tap factory setting 277 Volt

Figure 11. LP11 924 6&10 kVA: Output tap change

Figure 11a. LP11 924 6&10 kVA: Rear View

Figure 11b. LP11 924 6&10 kVA: 277 Vac output connection