5 - test screens, 1 - battery test, general, 2 - quick battery test – GE Industrial Solutions LP11 924 Series 6 & 10 kVA User Manual

Page 40

Advertising
background image

modifications reserved

OPM_LPU_11U_6K0_10K_1US_V010.Doc

39

User manual LP11 924 6 & 10 kVA UPS 1.0

Setting ‘YES’ means that the function is activated: the UPS will switch off during a
utility failure when the load is less than 2% of the maximum load. Range: YES/NO.

NO-LOAD SHUTDOWN
YES

If the UPS operates in parallel the no-load shutdown function is not

available. In this case do not activate this function: its setting should

read "NO".

AUTOMATIC BYPASS
ENABLED

Controls functioning of the automatic bypass switch. Range: ENABLED/DISABLED. If

the UPS is used as a frequency converter you may change the setting to ‘DISABLED’.

Bypass operation will then be inhibited and all alarms related to ‘bypass out of limits’
are suppressed.

The system can prompt for service to a user defined schedule.

Range: 8/12/16/20/24/28 months or DISABLED. To reset the timer: first select

“DISABLED” and subsequently set a new alarm interval.

SERVICE WARNING
DISABLED

5.5 - TEST SCREENS

These screens show the test procedure, either started from the service menu (front panel keys) or via the UPS monitoring

software (RS232/SNMP). The upper line indicates the kind of test, the second line its status.

Upper lines:

second line:


GENERAL SYSTEM

TEST START

the test will start soon

QUICK BATTERY

TEST ACTIVATED

the test is running

CALIBRATE BAT

TEST SUCCESFUL

the test has been completed successfully

BYPASS

TEST FAILED

the test has not been completed successfully

5.5.1 - BATTERY TEST, GENERAL

Automatic test: Every 500 operating hours the UPS conducts automatic battery tests to ensure that the batteries and the

wiring are able to support power failures. The tests do not cause any interruption in the functioning of the unit.

Manual test: A manual battery test can be activated

- either through an interface kit, via the RS232 or SNMP Interface Port (please refer to the manual of your

interface package),

- or via the front panel: see below

5.5.2 - QUICK BATTERY TEST

From the standard menu first enter the service menu (press the 'down' and 'Enter/Reset' keys simultaneously, then press

the 'down' key until the following screen appears:

QUICK BATTERY
TEST PRESS ENTER

QUICK BATTERY

TEST START

The ‘Enter/Reset’ key confirms the selection, and the screen shows: