User manual LP11 924 6 & 10 kVA UPS 1.0

Service information on internal timer.

TSTAMP Q4
6028773 1

FREQ RANGE: 2%

NO LOAD : 1

Frequency tracking range: output converter frequency will follow the bypass frequency
within these limits before returning to its own internal frequency. Standard setting:

nominal ±2%. Can be changed into nominal ±4% or ±6%. See 5.4.4 Set-up Menu.

No-load shutdown: after a 10 minutes delay the UPS will shut down during utility
failure if the load is < 2%. It will restart after the utility returns or when the unit is

switched off and on again.
Default setting = 1 (active). For disabling this feature see 5.4.4.

Start of the manual Quick Battery Test.
See for more information section 5.5.2 'Quick Battery Test'

QUICK BATTERY
TEST PRESS ENTER

Start of the manual Deep Battery Calibration Test.
See for more information sections 5.5.3 'Deep Battery Calibration Test'.

CALIBRATE BAT
PRESS DOWN+ENTER

Service information on internal UPS components.

PF1 THYRISTOR 1
BATT.THYRISTOR 0

Service information on internal UPS components.

VSS THYRISTOR 1
PF1. CONVERTER 0

Service information on internal UPS components
Batt.Charger: 0 = off, 1 = float charging; 2 = top charge, 3 = boost charging,

4 = maintenance charge

BAT CHARGER 1

INVERTER 0

Duration of latest test performed, hh/mm/ss.

LAST TEST TIME
0:00:00

The UPS transfers the load to bypass when the keys 'down' (2) and 'Enter/Reset' (3) on

the front panel are depressed simultaneously for approx. 1 second. If the bypass

supply is not within limits, the lower line will show the text 'UNAVAILABLE'.

FORCE BYPASS
Press DOWN+ENTER

Service set-up information whether the bypass is enabled (default) or disabled. If disabled:

UPS will NOT go to bypass. For disabling the bypass refer to the set-up menu (5.4.4).

AUTOMATIC BYPASS
ENABLED

Service set-up information about the total battery capacity. Information about the

actual battery charge condition. For changing the programmed battery capacity refer
to the set-up menu (5.4.4).

BATTERY 76Ah
BAT. CHARGER 86%

PLL LOCK SPEED
NORMAL

Service set-up information about frequency tracking speed for the inverter to follow

the bypass frequency, LOW (1Hz/sec.) is the normal value and default. HIGH (5Hz/sec.)
may be suitable if the UPS is connected to a generator with fast frequency changes

and the UPS must be synchronized to prevent alarms. For changing the lock speed

refer to the set-up menu (5.4.4).

ECO DISABLED
ENTER/RESET CHNG

Service set-up information about the ECO-mode. By pressing ‘Enter/Reset’ the ECO-mode

can be enabled or disabled, depending on the actual status. In this way the load will be
supplied by way of the electronic bypass. If the ECO-mode is disabled the load will be

supplied by the inverter. See also 5.6.5.

If RPA used, ECO mode must be set to “Disabled”

Service set-up information about the auto restart function. This function can be
switched on or off by pressing ‘Enter/Reset’, depending on the actual status. See also

4.5.6.1 step 6.

AUTO RESTART ON
ENTER/RESTART CHNG