User manual LP11 924 6 & 10 kVA UPS 1.0

5.4.4 - SET-UP MENU

To enter the set-up menu:

1. Be sure the UPS is switched off.

2. Press push-button 'Enter/Reset' (front panel) and then turn switch ‘UPS on/off’ (rear panel) into position ‘on’ (up). Keep

Enter/Reset pressed until set-up menu appears.

Using push-buttons 'up' and 'down' you can scroll through the several set-up screens, 'Enter/Reset' confirms a screen

choice. After selecting a set-up screen you can scroll through its settings using the push-buttons 'up' and 'down', a setting

is confirmed by pressing 'Enter/Reset'. To abort the set-up procedure (i.e. without changing the setting) just wait the 20

seconds time-out period after which the default screen will return.

The intro set-up screen. 'Enter/Reset' returns to the default screen. You can also wait
20 seconds: the time-out period of no key activity.

SETUP SCREENS
ENTER/RESET exit

Pressing ‘up’ displays the screens in the following order:.

A short reminder that the new settings will be valid immediately after depressing the

‘Enter/Reset’ key.

WARNING: OUTPUT
CHANGES ON LINE

Changes the language of the screen messages: you can select English, German,

French, Italian, Spanish.

LANGUAGE
ENGLISH

The system input voltage: Range 120/208/240/277 Vac.

INPUT VOLTAGE

277V

The system output voltage. Range: 120/208/220/230/240/277 Vac.

OUTPUT VOLTAGE
277V

The system output frequency. Range: 50/60 Hz.

OUTPUT FREQUENCY
60.0Hz

CAUTION

Changing of the output frequency can cause severe damage of

equipment connected to the UPS: Make sure that the new frequency is

suitable for the connected equipment.

FREQUENCE RANGE
2%

The frequency tracking range (in which the output converter frequency will follow the

bypass frequency). Range: 2/4/6 %.
If the bypass frequency is beyond the setting, the output converter will return to the

fixed crystal controlled frequency.

The frequency tracking speed range (in which the output converter frequency will

follow the bypass frequency).
Range: NORMAL (1Hz/sec), HIGH (5Hz/sec).

PLL LOCK SPEED
NORMAL

Battery capacity. Range: 7 through 590 Ah, in 1 Ah steps. For LP 6-11U

924

units the

battery capacity is 76Ah and for LP 10-11U

924

units it is 92Ah. This is set in the factory

and should not be changed.

BATTERY CAPACITY
76Ah

NOTE

If you proceed, the information about the actual battery condition (as

a result of a deep battery test) is lost. For more info see section 5.5.3

'Deep Battery Test'.

The fan speed. Range: 0 / 1. Proper setting optimizes the cooling capacity of the fans

installed.

DO NOT READJUST! Incorrect setting may lead to reduced lifetime of the

power semiconductors.

FAN CURVE