User manual LP11 924 6 & 10 kVA UPS 1.0
INPUT AND OUTPUT
NOT SYNCHRONIZED
The output converter frequency is not synchronized to the utility (input) frequency. In this
situation the automatic bypass switch is not able to transfer the load from output
converter to bypass and reverse: automatic bypass operation is inhibited: if for whatever
reason the output converter is unable to deliver the required output, output power is lost.
(see section 3.5).
Synchronization is only possible if the utility frequency remains within certain limits
(see chapter 10).
The remaining runtime. This figure is counted down during battery operation until
either the utility returns or the batteries are depleted.
BATTERY RUNTIME
LEFT: 0:09:41
The output is switched off due to a faulty situation, indicated by the second line.
OUTPUT OFF
NO INPUT POWER
The output will be switched off by a remote command (RS232/SNMP). The second line
indicates the time until shutdown.
PROG. SHUTDOWN
WITHIN 0:09:17
The output is switched off by a remote command (RS232/SNMP). The second line
indicates the time until wake-up.
PROG. SHUTDOWN
LEFT 0:14:03
The output is switched off by the 'no-load shutdown' feature: no input voltage and
load <2%. If the input voltage is restored, the output will be available again. See also
section 5.6.1.
SHUTDOWN
ALARM PRESS U
The wire on connector J3 pin 3-4 (rear panel, plug-in card –12 in Fig.19) is interrupted.
The output is no longer available. To restart the unit, restore the connection and turn
the on/off switch (7 in Fig.19) off and on again.
IMMEDIATE
SHUTDOWN
5.4.3 - SERVICE MENU
When the default screen is displayed you can enter the first service screen by depressing the keys 'down' (2) and 'Enter/Reset' (3)
simultaneously for approx. 1 second. Using the 'up' (4) and 'down' (2) keys you can scroll through several service screens.
The intro service screen. 'Enter/Reset' returns to the default screen.
SERVICE SCREENS
ENTER exit
The serial number of the UPS.
SERIAL NUMBER
L051U01/0020A030
Release number of the installed software and production code of the UPS.
SOFTWARE VERSION
R2.9; 640777
Service information about fan speed (min. 10, max. 30) and internal DC voltage.
FAN SPEED 10
INV.DC: + 375
Service information on internal temperature levels, values in mV over the temperature
sensors.
HEATSI.TEMP: 0
TRANSF.TEMP: 310
First line: service information on charger. ‘1’ = batteries have reached float voltage.
Second line: service information on output converter.
FLOAT CHARGE: 1
OUTPUT FAST : 0