User manual LP11 924 6 & 10 kVA UPS 1.0

10 - SPECIFICATIONS

UPS

: 6kVA

10kVA

Output power (kVA/kW)

: 6/4.8

10/8

AC input voltage

: 120/208/240/277 VAC

Input frequency

: 60/50 Hz

AC output voltage

: 120/208/220/230/240/277VAC

Output frequency

: 60/50 Hz

UPS efficiency (full load)

: 88.7%

88.7%

UPS efficiency on ECO mode (full load)

: 93%

94.2%

Line input breaker (C-type)

: 32A

63A

Bypass input breaker (C-type)

: 32A

63A

Battery safety fuse (F4A)

: 30A

30A

Battery safety fuse (F4B)

: 30A (spare)

30A

Internal safety fuse (F5A)

: -

30A

Internal safety fuse (F5B)

: 30A

30A

Input/output connectors

: terminals at rear of unit

INPUT

AC input voltage range (208V-240V)

at 100% load : 162 - 285 V

at 50% load : 146 - 285 V

at 20% load : 133 - 285 V

AC input voltage range (120V)

at 100% load : 81 - 141 V

at 50% load : 72 - 141 V

at 20% load : 66 - 141 V

AC input voltage range (277V)

at 100% load : 187 - 325 V

at 50% load : 166 - 325 V

at 20% load : 153 - 325 V

Input frequency range

: 40-70 Hz

Input current wave form

: sinusoidal

Input power factor

: ≥ 0.99

Max. input current at 100% load

120V

: 57A

89A

208V

: 33A

51A

240V

: 30A

44A

277V

: 23A

39A

Inrush current

: none

Rectified DC voltage out

: 380 V

BATTERY CHARGER

Characteristic

: U/I-characteristic, constant current charging until boost/float voltage, then

constant voltage charging and boost charge mode for fast recharging of batteries

DC input voltage range

: 350 - 450 V

DC output voltage at 20 °C

: float: 273 V, boost: 295 V

Output current limit (Adc)

: 4.2

4.2

OUTPUT CONVERTER

Output power at pf. = 0.8, VA*

: 6000

10000

Semiconductor

: IGBT

AC output voltage

: 120/208/220/230/240V/277 ± 1% static resistive load

120/208/220/230/240V/277 ± 2% measured crest load 2.5:1

120/208/220/230/240V/277 ± 2% dynamic mean deviation over one half cycle

for 100% of rated load applied or removed

Typical overload

: 110% ≥ 20 minutes

(temp. dependent)

130% ≥ 3.5 minutes

150% ≥ 2 minutes

Output frequency

: 60 or 50 Hz selectable, ± 0.1%, unless synchronized with the utility

Freq. tracking range

: ± 2/4/6% of nominal, user selectable

Output wave form

: sine wave

Max. phase difference input-output

: max 7°

Harmonic distortion

: 2% max. with linear load

Power factor range

: Any lagging or leading power factor permitted within the specified rating to pf. 0.5

Output derating altitude

: Till 1000m no derating

Above 1000m 12.5% per 1000m, max. 4000m

Protection

: Automatic shutdown (or transfer to bypass, if bypass is available) in case of

- low/high DC voltage

- overtemperature

- overload / short circuit

The output is protected against connection to the utility supply

* according to EN 50091-1