10 - specifications – GE Industrial Solutions LP11 924 Series 6 & 10 kVA User Manual
Page 49
modifications reserved
OPM_LPU_11U_6K0_10K_1US_V010.Doc
48
User manual LP11 924 6 & 10 kVA UPS 1.0
10 - SPECIFICATIONS
UPS
: 6kVA
10kVA
Output power (kVA/kW)
: 6/4.8
10/8
AC input voltage
: 120/208/240/277 VAC
Input frequency
: 60/50 Hz
AC output voltage
: 120/208/220/230/240/277VAC
Output frequency
: 60/50 Hz
UPS efficiency (full load)
: 88.7%
88.7%
UPS efficiency on ECO mode (full load)
: 93%
94.2%
Line input breaker (C-type)
: 32A
63A
Bypass input breaker (C-type)
: 32A
63A
Battery safety fuse (F4A)
: 30A
30A
Battery safety fuse (F4B)
: 30A (spare)
30A
Internal safety fuse (F5A)
: -
30A
Internal safety fuse (F5B)
: 30A
30A
Input/output connectors
: terminals at rear of unit
INPUT
AC input voltage range (208V-240V)
at 100% load : 162 - 285 V
at 50% load : 146 - 285 V
at 20% load : 133 - 285 V
AC input voltage range (120V)
at 100% load : 81 - 141 V
at 50% load : 72 - 141 V
at 20% load : 66 - 141 V
AC input voltage range (277V)
at 100% load : 187 - 325 V
at 50% load : 166 - 325 V
at 20% load : 153 - 325 V
Input frequency range
: 40-70 Hz
Input current wave form
: sinusoidal
Input power factor
: ≥ 0.99
Max. input current at 100% load
120V
: 57A
89A
208V
: 33A
51A
240V
: 30A
44A
277V
: 23A
39A
Inrush current
: none
Rectified DC voltage out
: 380 V
BATTERY CHARGER
Characteristic
: U/I-characteristic, constant current charging until boost/float voltage, then
constant voltage charging and boost charge mode for fast recharging of batteries
DC input voltage range
: 350 - 450 V
DC output voltage at 20 °C
: float: 273 V, boost: 295 V
Output current limit (Adc)
: 4.2
4.2
OUTPUT CONVERTER
Output power at pf. = 0.8, VA*
: 6000
10000
Semiconductor
: IGBT
AC output voltage
: 120/208/220/230/240V/277 ± 1% static resistive load
120/208/220/230/240V/277 ± 2% measured crest load 2.5:1
120/208/220/230/240V/277 ± 2% dynamic mean deviation over one half cycle
for 100% of rated load applied or removed
Typical overload
: 110% ≥ 20 minutes
(temp. dependent)
130% ≥ 3.5 minutes
150% ≥ 2 minutes
Output frequency
: 60 or 50 Hz selectable, ± 0.1%, unless synchronized with the utility
Freq. tracking range
: ± 2/4/6% of nominal, user selectable
Output wave form
: sine wave
Max. phase difference input-output
: max 7°
Harmonic distortion
: 2% max. with linear load
Power factor range
: Any lagging or leading power factor permitted within the specified rating to pf. 0.5
Output derating altitude
: Till 1000m no derating
Above 1000m 12.5% per 1000m, max. 4000m
Protection
: Automatic shutdown (or transfer to bypass, if bypass is available) in case of
- low/high DC voltage
- overtemperature
- overload / short circuit
The output is protected against connection to the utility supply
* according to EN 50091-1