8.5 - STORAGE
CAUTION
In case of storage, pay attention to:
Always store the UPS in a dry location with the batteries in a fully charged state, storage temperature must be within -20
and +45°C (-4°F and 113°F). Storing the unit for a period exceeding 3 months can reduce the life of the batteries. To
maintain their normal life expectancy, the batteries must be recharged periodically:
- if the storage temperature is within -20 and +30°C (-4°F and 86°F): every 6 months, for 24 hours,
- if the storage temperature is within -20 and +45°C (-4°F and 113°F): every 4 months, for 24 hours.
8.6 - RECYCLING THE UPS AT THE END OF SERVICE LIFE
NOTE
This product has been designed to respect the environment, using materials and components
respecting eco-design rules. It does not contain CFCs (Carbon Fluorine Chloride) of HCFCs (Halogen
Carbon Fluorine Chloride).
The batteries contain lead, which is a harmful substance for the environment.
Proper disposal or recycling of the batteries is required. Refer to your local codes for disposal
requirements.