8.5 - STORAGE

CAUTION

In case of storage, pay attention to:

Always store the UPS in a dry location with the batteries in a fully charged state, storage temperature must be within -20

and +45°C (-4°F and 113°F). Storing the unit for a period exceeding 3 months can reduce the life of the batteries. To

maintain their normal life expectancy, the batteries must be recharged periodically:

- if the storage temperature is within -20 and +30°C (-4°F and 86°F): every 6 months, for 24 hours,

- if the storage temperature is within -20 and +45°C (-4°F and 113°F): every 4 months, for 24 hours.

8.6 - RECYCLING THE UPS AT THE END OF SERVICE LIFE

NOTE

This product has been designed to respect the environment, using materials and components

respecting eco-design rules. It does not contain CFCs (Carbon Fluorine Chloride) of HCFCs (Halogen

Carbon Fluorine Chloride).

The batteries contain lead, which is a harmful substance for the environment.

Proper disposal or recycling of the batteries is required. Refer to your local codes for disposal

requirements.

GE Digital Energy, in compliance with environment protection recommends that the UPS equipment, at

the end of its service life, must be recycled conforming to the local applicable regulations.