User manual LP11 924 6 & 10 kVA UPS 1.0

5.4 - USE

The UPS is operated via the push-buttons (fig. 19, 2-3-4) and the LCD display (front panel, 1). Furthermore the UPS can be

controlled via the RS232/contact interface port (12a in Fig.19). For more information see 6.1.

The menus on the display can be divided into 5 groups:

1 Standard screen

2 Information menu (section 5.4.1)

3 Status- and alarm menu (section 5.4.2)

4 Service menu (section 5.4.3)

5 Set-up menu (section 5.4.4)

The standard screen shows UPS model and actual load.

LP 6-11U 924
LOAD 37%

5.4.1 - INFORMATION MENU

When the default screen is displayed the first information screen can be entered by depressing the 'up' key (front panel,

4). Using the 'up' and 'down' keys (front panel, 4 and 2) you can scroll through several information screens. After the last

information screen the default screen will appear.

The screens display the following information:

Utility voltage and utility frequency, and the power delivered by the utility.

INPUT LINE 277V
2.45Kw 60Hz

Output voltages and output frequency, and the power delivered by the UPS (as % of
the nominal UPS rating).

OUTPUT LINE 277V
LOAD 50% 60.0HZ

The temperature near the batteries, the battery voltage and the battery current
(charging: + value, discharging: - value).

BATTERY 23°C
271V 1.9A

The remaining battery runtime (or autonomy) during a utility failure.

AUTONOMY TIME
LEFT 5:27:00

The total operating time of the UPS.

OPERATING TIME
0YEAR 29DAYS