GE Industrial Solutions LP11 924 Series 6 & 10 kVA User Manual

Page 50

Advertising
background image

modifications reserved

OPM_LPU_11U_6K0_10K_1US_V010.Doc

49

User manual LP11 924 6 & 10 kVA UPS 1.0

UPS

: 6kVA

10kVA

AUTOMATIC BYPASS SWITCH

The automatic switch provides transfer of the load to the utility voltage without any interruption of the supply. The transfer is initiated by a

signal from the output converter protection circuit in case of an overload or high temperature.

When the conditions return to normal the load is automatically transferred back to the output converter. The automatic bypass switch can

be disabled by the end-user.

Bypass voltage limits

: -15%, +10% of nominal

Transfer transients

: typically 2% mean deviation over one half cycle.

Frequency tracking range

: ± 2/4/6% of nominal (user selectable)

Slew rate

: max. 1Hz/sec or 5Hz/sec (user selectable)

BATTERY

Battery type

: Sealed and maintenance free

Nominal voltage (V) / capacity (Ah)

: 12/76

12/91

Number of batteries

: 20

20

Battery part number

: BATLP116-924

BATLP1110-924

Battery recharge time

: 24 hours for 80% capacity

Battery service life

: up to 6 years (depending on operating conditions)

Battery discharging

: self discharge current ≤ 100 mA

End of discharge voltage

:Load dependent 10.5Vdc < 0.2 CA till 9.0 Vdc > 2 CA

Load on UPS

: Runtime in minutes

VA / Watts

1000 / 800

: 700

850

2000 / 1600

: 450

530

3000 / 2400

: 300

350

5000 / 4000

: 180

220

6000 / 4800

: 150

160

8000 / 6400

: -

120

10000 / 8000

: -

93

BATTERY cabinet

Dimensions (HxWxD, mm)

: 1092x1016x826

Dimensions (HxWxD, inch)

: 43x40x32.5

Weight without battery (Kg)

: 148

148

Weight without battery (lbs)

: 326

326

Weight with battery (Kg)

: 699

802

Weight with battery (Lbs)

: 1538

1764

ENCLOSURE

Sheet steel cubicle 208/240V I/P

: VSD2

VSD2

Sheet steel cubicle 120/277V I/P

: VSDT2 + VSD2

VSDT2 + VSD2

Color front

: RAL 9006 (aluminum)

Color cabinet

: RAL 9010 (white)

Protection

: IP 20

Dimensions (HxWxD)

: Refer table 5

Weight (without batteries, Kg)

: Refer table 5

GENERAL DESIGN CRITERIA

Mechanical

: IP20

Humidity

: 95% no condensing

Safety

: UL 924, IEC 60950

Surge capability

: 6kV 1.2/50µs; 3kA 8/20µs; IEEE C62.41 (6kV, 100kHz)

EMC

: FCC part 15, class A

ENVIRONMENT

Ambient temperature

: 0 to +40°C (32 to 104°F). For optimal backup time 20 to 30°C (68°F to 86°F) is

recommended for battery

Audible noise at 1 meter

: 40 - 50dB(A), the audible noise is load and temperature dependent

Cooling air ((25°C/77°F - 30°C/86°F)

: 330m

3

/h or 194CFM