ELECTRICAL INSTALLATION & WIRING

Page

3-1

3

LS300 User’s Guide

3

Electrical Installation & Wiring

Electrical Installation & Wiring Sequence:

Basic Installation & Wiring

Follow the instructions here to wire the LS300 Auto-Learn console, the

LSU300 Transducers from each STP containment sump, the Dispenser

Hook Inputs, and Console Power Input. (see Figure P-1 & Figure 3-1).

Ask the service tech to do “mechanical - pump/dispenser” work if

appropriate.

1.)

All cables from the LSU300 transducer to the LS300 console must be installed in metal conduit in

countries requiring CE compliance. Power and communication wires do not need metal conduit

unless it is required by local code.

WARNING

Avoid personnel injury or property damage: ALWAYS secure the hazardous work area

from moving vehicles. This equipment is usually mounted underground, therefore, reduced visibility

puts service personnel working on this equipment in danger from moving vehicles entering the work

area. Use Safety Cones, Barricades, Warning Signs, and Safety Tape, and block access with

Barricades / service vehicles to the work area to avoid injury or property damage.

2.)

At the electrical power panel: locked-out & Tag POWER OFF for the STP’s, Pump Controllers, and

Dispensers.

ELECTRICAL DANGER

Hook inputs are 120/240 Vac. Disconnect all high voltage sources before

accessing internal electronics

DANGER

Electronic line leak detectors start submersible pumps automatically to run leak-tests at

full line pressure. Automatic pump starts occur between periods of product dispensing when there is

no product being dispensed. BEFORE performing any installation or service (such as replacing

fuel-filters) – tag and lock-out all electrical power sources to the submersible pump(s), pump

controllers, and dispensers and relieve fuel-line pressure. Failure to turn off power and

relieve fuel-line pressure before work is started can result in: pressurized fuel spills (an

environmental hazard associated with costly cleanups), and fire or explosion hazard that may

result in injury or death.

3.)

If not done during Mechanical Installation, chapter 2, Run 3 conductor shielded cable from each

Explosion proof/Weatherproof Junction Box in the STP sump where the LSU300 Transducer is

installed, to the LS300 console for Transducer wiring leaving about an 8 inch (203 mm) service loop

(Figure 3-2 & 3-3). Label/Mark each cable jacket with the Tank # / LSU300 Transducer number.

1

TS-LS300

Auto-Learn

Console

Inputs (#1-4):

Lines (#)

Hooks (#)

Power