Franklin Fueling Systems TS-LS300 AutoLearn Pressure-Based Electronic Line Leak Detector System Users Guide User Manual

Page 7

Advertising
background image

P

Page

P-4

PREFACE

LS300 User’s Guide

the alarm horn can be silenced by pressing the Test/Reset push-button on the appropriate channel,

which will silence the alarm horn and can start a new manual Line Leak Test.

The LS300 System Applications – 5 block diagrams

The block diagrams on the next page, Figure P-1, show the 5 different applications possible with this

equipment. Only block diagram #1, Basic Auto-Learn electronic Line Leak Detector (LLD) console,

is covered in this manual, See TS-TPI, TS-1001-, TS-2001, or STP controller User guides for more

information on the other applications. The possible Applications are:

# 1

Basic Auto-Learn electronic Line Leak Detector (LLD) console

# 2

One LS300 Auto-Learn console with TS-TPI plus an INCON ATG (Automatic Tank
Gauge) console for LLD interface

Note: TPC is the designation for a Turbine Pump Controller throughout this

manual

# 3

One LS300 Auto-Learn console with TS-TPI for Turbine Pump Controller (TPC)
interface and an INCON ATG console for LLD and Pump Controller interface

# 4

Two LS300 Auto-Learn consoles for support of up to 8 lines: one console has the
TS-TPI interface circuit board enabling connection to the other LS300 console via a
special RS-232 cable and to the INCON ATG console via RS-485 communication
for LLD interface

# 5

Two LS300 Auto-Learn consoles for line leak detection of up to 8 lines: one console
has the TS-TPI interface circuit board for connection to the other LS300 console via
a special RS-232 cable and connects to the INCON ATG console via RS-485
communication for LLD interface and for Turbine Pump Controller control

TABLE P-1 Console Channel X - Test/Reset PB

See the
Operation
section in this
manual or the
Quick
Reference
Guide

Push

#

Times

Effect

1

Silences Alarm Horn

2

Gross (3 gph / 11 Lph) Line Leak Test

3

Monthly (0.2 gph / 0.8 Lph) Line Leak Test

4

Annual (0.1 gph / 0.4 Lph) Line Leak Test

Advertising