4line calibration – Franklin Fueling Systems TS-LS300 AutoLearn Pressure-Based Electronic Line Leak Detector System Users Guide User Manual

Page 27

Advertising
background image

LINE CALIBRATION (LEARN MODE)

Page

4-1

4

LS300 User’s Guide

4

Line Calibration

NOTE !

Before Calibrating a Line:

1.)

A PRECISION LINE TEST MUST BE CONDUCTED on each line before installing the LS300 Auto-

Learn

®

LLD system for the first time, or before replacing, or before adding a new LSU300 LLD

Transducer.

2.)

USE A PRESSURE GAUGE TO VERIFY THAT EACH LINE IS STABLE. THE PRESSURE

CHANGE WITHIN THE PIPELINE AFTER 5 MINUTES OF PUMP-OFF MUST BE LESS THAN 5

PSI. The LS300 Auto-Learn

LLD system will not calibrate properly unless the product is stable in

pipeline.

3.)

A LEAK GENERATOR DEVICE/CALIBRATION KIT (SUPPLIED) MUST BE INSTALLED AT THE

STP TO PERFORM CALIBRATION OR MANUAL TESTING. Follow steps 1 to 12 and see Photo 4-1

for this installation.

4.)

Turn on and CALIBRATE ONLY ONE CHANNEL AT A TIME! When that channel is complete, turn

off that channel and turn on the next channel to calibrate.

5.)

ALWAYS PLACE THE RUN STOP (SW3) IN THE STOP POSITION, AND WAIT 10 SECONDS

BEFORE MOVING ANY OTHER SWITCH.

Configuration Slide-Switches

RUN STOP SW3 always position to STOP {down}

and wait 10 seconds before moving any other slide-

switch

LEARN CH-N DETECT

SW4 = Channel-1 / Line #1

SW5 = Channel-2 / Line #2

SW6 = Channel-3 / Line #3

SW7 = Channel-4 / Line #4

CHANNEL ENABLE SW2

miniature slide-switches for

channels/lines # 1 to 4

(ON / ENABLE = up & OFF

= down)

The Run Stop and Learn
Detect-switches are in the
console at the upper-left.

Photo 4-1 Channel / Learn

ON

OFF

NOTE