ELECTRICAL INSTALLATION & WIRING

LS300 User’s Guide

Figure 3-3 LSU300E Explosion Proof Transducer Wiring at

Explosion Proof Junction Box

Wire Explosion Proof LSU300E transducers only to TS-LS300E consoles in accordance with

applicable standards. Explosion proof J-Boxes and conduit fittings must be used in this

application in hazardous locations. This wiring does not require separation from other non-

intrinsically safe wiring.

This method can be used for retrofit installations where separate conduit is not available.

NOTE

Beldon #9363-22 AWG,
#9364-20 AWG, #9365-18AWG
or equivalent recommended.
Max Cable length is 500 feet.

3 CONDUCTOR
CABLE 6FT
(1.83 meters)
Supplied

Syphon

Plug

Tank

Plug

LS300E Auto-Learn
Line Leak Detector
Console (CU)

Follow all federal, state, and local
laws & codes governing the
installation of this product & the
entire system.

Maximum safe area voltage must
not be greater than 250 Vrms.

TO SPLICE:
INSERT
UNSTRIPPED
WIRES & USE
SLIP-JOINT
PLIERS TO SEAT BLACK PIECE

BLK

SHIELD

WHT

BL

K

SH

IEL

D

WHT

RED

Annunciator States/Conditions

Auto-Learn
Line Leak Detector

4

3

2

1

TS-LS300

TEST

/

RESET

TEST

PASSED

ALARM

FAILED

Annunciator Legend

HI

PUMP ON

LO

RE

D

ALARM

FAILED

ALARM

FAILED

ALARM

FAILED

INTELLIGENT CONTROLS

PRESSURE

PRESSURE

PRESSURE

PRESSURE

HI

PUMP ON

HI

PUMP ON

HI

PUMP ON

TEST

/

RESET

TEST

/

RESET

POWER

TEST

/

RESET

LO

LO

TEST

PASSED

TEST

PASSED

LO

TEST

PASSED

R

No-Strip Electrical
Connectors inside

Explosion Proof

J-Box

(Junction Box)

5 FT (1.53 meters)

MAX from LSU300E

Transducer

LSU300E

Pressure

Transducer

STP

HOUSING

Coupling

EYS (Epoxy Y Seal)

Fitting TYP

3/4 inch NPT Conduit

(DN20NPT)

w/ Explosion Proof

Fittings

- Typical -