LINE CALIBRATION (LEARN MODE)

Page

4-3

4

LS300 User’s Guide

6.)

If not done in chapter 3, Wire the dispenser hook signal to the proper channel associated with the

product line being worked on (Figure 4-2).

7.)

Turn power on at the load center to LS300 Auto-Learn

®

, pumps and

related equipment for product with Leak Generator Device installed.

Turn RUN/Stop switch to STOP. For the channel to be learned install

the Leak Generator Device in the line, if not already done, set the

CHANNEL ENABLE Switch to ON, the LEARN/DETECT Switch to

LEARN (See Figure 4-2) and set all other channel enable switches to

OFF. Wait 10 seconds, and then set the STOP/RUN switch to RUN

(See Figure 4-3). Verify the Calibration Kit is secure to a suitable

container and energize the submersible for this product. Check

Transducer and Leak Generator Device installation for leaks. If there

Figure 4-1 Leak Generator Device {Calibration Kit} & Pressure Gauge at STP

LEAK
GENERATOR
CALIBRATION
KIT AT STP
(NEEDLE VALVE)
...ONLY ONE LINE
IS CALIBRATED AT
A TIME DURING
LS300 AUTO-LEARN
MODE

LS300
CALIBRATION KIT
ABOUT 72 INCHES
(182.88 cm) LONG
REF: 020-0315
1 REQUIRED
PER SYSTEM

PRESSURE
GAUGE

Figure 4-3 Run/Stop

Switch