Franklin Fueling Systems TS-LS300 AutoLearn Pressure-Based Electronic Line Leak Detector System Users Guide User Manual
Page 29
LINE CALIBRATION (LEARN MODE)
Page
4-3
4
LS300 User’s Guide
6.)
If not done in chapter 3, Wire the dispenser hook signal to the proper channel associated with the
product line being worked on (Figure 4-2).
7.)
Turn power on at the load center to LS300 Auto-Learn
®
, pumps and
related equipment for product with Leak Generator Device installed.
Turn RUN/Stop switch to STOP. For the channel to be learned install
the Leak Generator Device in the line, if not already done, set the
CHANNEL ENABLE Switch to ON, the LEARN/DETECT Switch to
LEARN (See Figure 4-2) and set all other channel enable switches to
OFF. Wait 10 seconds, and then set the STOP/RUN switch to RUN
(See Figure 4-3). Verify the Calibration Kit is secure to a suitable
container and energize the submersible for this product. Check
Transducer and Leak Generator Device installation for leaks. If there
Figure 4-1 Leak Generator Device {Calibration Kit} & Pressure Gauge at STP
LEAK
GENERATOR
CALIBRATION
KIT AT STP
(NEEDLE VALVE)
...ONLY ONE LINE
IS CALIBRATED AT
A TIME DURING
LS300 AUTO-LEARN
MODE
LS300
CALIBRATION KIT
ABOUT 72 INCHES
(182.88 cm) LONG
REF: 020-0315
1 REQUIRED
PER SYSTEM
PRESSURE
GAUGE
Figure 4-3 Run/Stop
Switch