Franklin Fueling Systems TS-LS300 AutoLearn Pressure-Based Electronic Line Leak Detector System Users Guide User Manual

Page 23

Advertising
background image

ELECTRICAL INSTALLATION & WIRING

Page

3-5

3

LS300 User’s Guide

4.)

Remove a portion of the cable jacket (service-loop) inside the J-Box, and install the no-strip electrical

connectors inside the J-Box (see Figures 3-2 & 3-3).

5.)

Verify that all connections are correct and that the like colored and unstripped wires are fully inserted

into the no-splice connectors (RED to RED, WHITE to WHITE, BLACK TO BLACK, and SHIELD

DRAIN to SHIELD DRAIN) and are spliced together... make sure that the black, oval-shaped

compression part is firmly seated down into the connector with slipjoint pliers (see Figures 3-2 & 3-

3). Install J-Box cover after wire-splicing is completed and checked.

6.)

Remove the metal Terminal Safety Guard and Wire LSU300 Transducers to the Transducer Input

channel terminals inside the LS300 console. See Figure 3-4 for Tank, Line, and Product

associations, and TABLE 3-1 for wiring. Maintain these associations accurately when wiring

Transducer and Hook Input terminals.

Channel N must operate the STPs at Tank/Line N

A.)

Strip off 3/16 of a inch (5 mm) of insulation from the ends of each conductor

B.)

Wire Transducers # 1 – 4 (see Figure 3-4). Make sure all wires

are fully inserted and clamped at the terminal block. Make sure

no stray strands of wire are shorting to adjacent terminal block

connections.

C.)

Install the metal Terminal Safety Guard after verifying all

Transducer Input Channel wiring is correct

D.)

Verify that all splices in the manhole Junction Boxes are

accurate

E.)

Lastly, install the Explosion proof/Weatherproof Junction Box

Covers

WARNING

Never power up the LS300 console when the terminal

safety guard is removed

Basic Installation & Wiring – all Applications (Continued... )

NOTE

Photo 3-3

Transducer Inputs

Advertising