Franklin Fueling Systems TS-LS300 AutoLearn Pressure-Based Electronic Line Leak Detector System Users Guide User Manual

Page 40

Advertising
background image

6

Page

6-2

TROUBLESHOOTING

LS300 User’s Guide

2. With an ohmmeter, test for shorts
between the three transducer wires, and
each wire to chassis ground. If a short is
found, test the connection between the
transducer and the field wiring, and
determine if the short is in the field wiring,
or internal to the transducer. Visually
inspect all wire connections. Repair any
loose or broken wire nut connections. If
the short appears to be internal to the
transducer, call Technical Support at (800)
984-6266.

3. With Circuit breaker to the LS300 console locked out and tagged, remove the
barrier to the transducer terminal blocks, disconnect transducer and measure ohms
from JP2, 4, 6, or 8 to channel 1, 2, 3, or 4 signal terminal block (see Figure 4-2 for

Transducer

Power to

Signal from

Channel

Transducer

Transducer

1

JP1

JP2

2

JP3

JP4

3

JP5

JP6

4

JP7

JP8

Figure 6-3

Test Point Identification

JP1

JP2

JP3

JP4
JP5

JP8

Figure 6-2

Test Point locations

JP6

JP7

Run Stop

Switch

Test Point

Locations

Advertising