LS300 User’s Guide

Pressure Transducer

Specifications

Model LSU300 Transducer

Approvals:

Electrical Specifications

Input Power

= 10 to 32 VDC

Output Signal

= 1 to 5 VDC

Signal Ground = Ground
Output Load

= 10K ohm output load

Output Noise

= < 2 mV

Current

= < 10ma

Insulation color:

Red

= Input Power

= V+

White

= Output Signal

= Signal

Black

= Signal Ground

= Ground

Bare Wire

= Shield Drain

= Ground

Unit is Reverse-Polarity protected

Applicable Liquid Products:

Petroleum (Gasoline, Diesel Fuel, Kerosene, Fuel
Oil, #2 Fuel Oil)

Accuracy:

0.5% FS (FS=Combined Linearity, Hystereses
and Repeatability)

Auto-Learn

®

Console

Specifications

Mechanical Specifications

Inches & ( mm):

Enclosure

11.75H x 10.75L x 3.75D
(298H x 273L x 95D)

Encl. w/ Door

12H x 11L x 4D
(305H x 279L x 102D)

Pressure Transducer

Specifications

Stability:

0.25% FS over full operating temperature

Materials Used:

Housing = Anodized Aluminum
Pressure Transducer (wetted portions) =

17-4

PH or 316 Stainless Steel

Environmental Specifications

Storage Temperature:

-67° to 185° F (-55° to 85° C)

Operating Temperature:

-40° to 149° F (-40° to 65° C)

Operating Pressure:

Normal 25 to 29 psi (1.7 to 2.0 Bar)
Transducer burst 500 psi (34.5 Bar)

Vibration:

10 G peak, 20 to 2000 Hz

Safety

LSU300 transducers are Intrinsically Safe for
installation in: Class I, Division 1, Group D (EU
Group IIA) hazardous locations, and
LSU300E transducers are Explosion Proof

Mechanical Specifications

inches:

(mm):

6.25H x 2NPT

(159H x DN50NPT)

H

L

D

Dispenser

Hooks

LSU300
transducers

RS232
Comm Port

Optional

TS-TPI

to

TS

Console

Input Power

2 INCH NPT

(DN50 NPT)

6.25

INCHES

(159

mm)

3/4 INCH

NPT

(DN20NPT)

5.13

INCHES

(130

mm)

2-3/8

INCHES
(70 mm)

ACROSS

FLATS

Advertising