Franklin Fueling Systems TS-LS300 AutoLearn Pressure-Based Electronic Line Leak Detector System Users Guide User Manual
Page 25
ELECTRICAL INSTALLATION & WIRING
Page
3-7
3
LS300 User’s Guide
Basic Installation & Wiring (Continued... )
8.)
Wire Console Power to the Power Input terminals
inside the LS300 console (see Figure 3-4):
A.)
Install / use a 10 ampere Circuit Breaker at
the Electrical Power Panel that is
dedicated/and used only for the LS300
Console(s).
ELECTRICAL DANGER
Match the voltage
shown on the Lower Left side label only when
selecting the console input power source,
otherwise damage to the LS300 console will
result. Any equipment damage caused by using
the incorrect input power source is not be
covered under warranty.
CAUTION
DO NOT use this circuit breaker for any other equipment, otherwise electrical noise
may affect the operation and reliability of the LS300 LLD system!
B.)
Remove the clear plastic, Terminal Safety Guard at the console and run wire within 1/2 inch
or 3/4 inch ( mm) RMC — size wire to the circuit breaker used and length of run (14 gauge is
recommended).
C.)
Wire according to TABLE 3-1 for 120 v power or TABLE 3-2 for 240 v power:
TABLE 3-1 LS300 Console Input Power From/To Wire List 120
Vac
TABLE 3-2 LS300 Console Input Power From/To Wire List 240
Vac
SW1
F1 F2
Photo 3-5
Input Power