Franklin Fueling Systems TS-LS300 AutoLearn Pressure-Based Electronic Line Leak Detector System Users Guide User Manual

Page 5

Advertising
background image

P

Page

P-2

PREFACE

LS300 User’s Guide

General Overview

The TS-LS300 Auto-Learn

®

Line Leak Detector (LLD) is a precision electronic line-leak-detection

system that is produced for installation in a petroleum pumping system. The Auto-Learn Line Leak

Detector automatically monitors at certain times and will indicate pipeline leaks should a leak occur.

An alarm indicator lights, an audible alarm horn sounds, and positive pump shutdown happens when

a leak is detected. This complies with U.S. EPA requirements 280.41(b) & 280.44(a) for automatic

leak detection in pressurized piping. After installation, the user of the leak detector must monitor the

system to ensure that any leak alarm and pump shutdown (indicating a leak in the pipeline) is dealt

with promptly.

The Auto-Learn LLD can detect a leak from the STP check valve to the solenoid valve at the

dispenser, assuming no other Normally Closed valve is in the pipeline system. The Auto-Learn LLD

does not detect leaks from the fuel storage tank or the from the submersible pump before the output

check valve. The Auto-Learn LLD is used with motor fuels.

The system includes a 2 or 4 channel LSU300 console with stick-on Product ID Labels, Danger

Labels, one Auto-Learn Calibration Kit (leak-generator), 2 to 4 Needle Valve Kits, no-splice

connectors, and 2 to 4 LSU300 pressure-transducers as specified at time of order. Each channel will

monitor one piping system or product line. All line leak detectors must be tested upon start-up, and

routinely thereafter (at least annually) under NFPA standards. These NFPA and other industry

testing practices must be followed by the installer and the end user. A leak detector is not a

substitute for compliance with prudent industry practices. Fuel inventory reconciliation checks must

be performed on a daily basis by comparing dispenser meter totalizers with fuel volume changes in

the underground tank.

The Auto-Learn LLD pressure transducer is manufactured in two different versions:

1)

The TS-LSU300 pressure transducers are Intrinsically Safe (I.S.) for U.S. and
international markets and are for use only with the TS-LS300 version console

2)

The TS-LSU300E pressure transducers are Explosion Proof for Canadian and
U.S. markets and are for use only with the TS-LS300E version console

Wire Intrinsically Safe LSU300 transducers only with TS-LS300 consoles... physical

separation of transducer cables from non-intrinsically safe circuits is also required.

Wire Explosion Proof LSU300E transducers only with TS-LS300E consoles in accordance

with applicable standards... use of explosion proof J-Boxes and conduit fittings in hazardous

locations. This wiring does not require separation from other non-intrinsically safe circuit wiring. This

method can be used for retrofit installations where separate conduit is not available.

This Installation and Owner’s Manual gives instructions for, site assessment and preparations,

installation, wiring, calibration, and operation. Each section gives step by step process to

successfully complete the section. A troubleshooting guide is included if difficulties are encountered.

NOTE