Aappendix a, Technical specifications, Ls300 auto-learn – Franklin Fueling Systems TS-LS300 AutoLearn Pressure-Based Electronic Line Leak Detector System Users Guide User Manual

Page 46: Line leak detector

Advertising
background image

APPENDIX A

Page

A-1

A

LS300 User’s Guide

A

Appendix A

LS300 Auto-Learn

®

Line Leak Detector

Technical Specifications

Auto-Learn

®

Console

Specifications

Models: LS300 (I.S.) & LS300E (ExP)

Approvals:

Electrical Specifications

Input Power:

L1

= 115 VAC +15%, –10% or

230 VAC +15%, –10% {

@

SW1}

= 0 VAC {N = Neutral}

Ground (2)

= 0 VAC (1 Terminal = Safety Gnd)

Frequency

= 50 / 60 Hz (either)

Current

= 1 A {115 VA} Maximum

WARNING

Match the line voltage

power ratings printed on the Serial Number
label when wiring to the console input
power terminals. Avoid voiding the
warranty & equipment damage – DO
NOT
use an incorrect voltage source!

Electrical Interface

RS232 Communication Port:

Bidirectional communications through 9-pin male
connector at bottom of console {baud rate = 4800,
format 8N1 (8 data bits, no parity, 1 stop bit)}

Optional RS485 Turbine Pump

Interface (TPI):

TS-TPI 3-wire input/output from to

FE Petro pump controllers

TS-TPI 3-wire input/output to Tank

Sentinel TS-LLD terminals

Dispenser Hook Interface:

1 to 4 channels, 2 wire, 115/230 VAC

Line Leak Test types:

Gross 3 gph (11 lph) Manual & Auto

{after every dispense or every 45 min’s}

Monthly 0.2 gph (0.8 lph) Manual & Auto

{3 hours after Gross test completes}

Annual 0.1 gph (0.4 lph) Manual & Auto

{3 hours after Monthly test completes
...6 hours total}

Number of Lines Monitored:

1 to 4 LSU300 Pressure Transducers

Alarm Annunciation:

Piezoelectric 90 Db audio output at 10 cm and
activates under the following alarm conditions:
after a Gross Leak Test fails (3 gph/11 lph),
after a Monthly Leak Test fails(0.2 gph/0.8 lph),
after Annual Leak Test fails (0.1 gph/0.4 lph)
when a Pressure Transducer is not sensed
when a Line fails to hold pressure
insufficient line pressure to conduct test

1 to 4 Channel Test/Reset push-
buttons silence alarms

Environmental Specifications

Storage Temperature:

-4° to 140° F (-20° to 60° C)

Operating Temperature:

32° to 122° F (0° to 50° C)

Operating Humidity:

0 to 95 %, non-condensing

Pollution Degree:

Category 2 per IEC 60664

Console Cleaning:

Cloth dampened slightly in mild detergent

Splash Resistance:

Not to be exposed to direct spray, splash, or drips

Console Location:

Indoors: office, or nonhazardous industrial
environment (or outdoors within a Nema 4x
enclosure) no further than 500 feet (152.4 m) from
any STP housing/LSU300 transducer

WARNING

The console must be

mounted in a location where explosive, or
flammable vapors are not present
otherwise, an explosion hazard will be
created which could result in property
damage, injury, and death.

Safety

Circuits Intrinsically Safe for LSU300 Transducers
installed in: Class I, Division 1, Group D (EU
Group IIA) hazardous locations,
LS300E for Explosion Proof Transducers

L2 or N

NOTE