8.1

Connection with AUMA plug/ socket connector (S, SH, SE)

Before mains connection

Check whether type of current, supply voltage, and frequency comply with
motor data (refer to name plate at motor):

Opening the terminal compartment

.

Loosen bolts (1) and remove cover (figure G).

.

Loosen screws (2) and remove socket carrier from cover.

.

Insert cable glands suitable for connecting cables
(The enclosure protection stated on the name plate is only ensured if suitable
cable glands are used.).

.

Seal cable entries which are not used with suitable plugs.

Multi-turn actuators SA 07.1 – SA 30.1/ SAR 07.1 – SAR 30.1

Operation instructions

with actuator controls AUMA MATIC AM 01.1 / AM 02.1

17

VD00 63-4/45
Art. No.: Z006.413
3 ~ 480V

60Hz

0.09 kW
Y 0.60A

Current type/mains voltage/mains frequency

NEMA 4X
Thermal protection: Th
Insulation class: F

Enclosure protection

Figure F-1: Version SH (standard)

Figure F-2: Version S

Figure F-3: Version SE

Figure G: Opening the terminal compartment

Cover

(1)

Socket carrier

(2)

Cable gland and
screw plug
in enclosure protection
according to name plate