22.3 Setting ON and OFF times

ON and OFF times can be set independently of each other between 1 – 30 sec-
onds at the 4 potentiometers R10 to R13.

Clockwise rotation:

Time extension

Counterclockwise rotation:

Time reduction

R10 (t-off)

: OFF time in direction OPEN

R11 (t-on)

: Running time in direction OPEN

R12 (t-off)

: OFF time in direction CLOSE

R13 (t-on)

: Running time in direction CLOSE

51

Multi-turn actuators SA 07.1 – SA 30.1/ SAR 07.1 – SAR 30.1

Operation instructions

with actuator controls AUMA MATIC AM 01.1 / AM 02.1

Figure AN: Cover plate for timer A1.6

R 10
R 11

R 12
R 13