3 setting on and off times – AUMA Electric multi-turn actuators SA 07.1 - 16.1_SAR 07.1 - 16.1 MATIC AM 01.1 - 02.1 User Manual

Page 50

Advertising
background image

22.2 Setting start and end of stepping mode via DUO limit switching (option)

Start and end of stepping mode can also be set via external switches
(use potential-free contacts).

Direction OPEN, first normal operation then stepping mode

.

Run valve in direction OPEN to the desired start of stepping mode.

.

Press down

and turn setting spindle K (figure AM) with screw driver

in direction of arrow, thereby observe LED V22 (figure AL).
Start of stepping mode in direction OPEN is set correctly if the LED changes
from off to on (see sketch on the left).

Direction CLOSE, first normal operation then stepping mode

.

Run valve in direction CLOSE to the desired start of stepping mode.

.

Press down

and turn setting spindle G (figure AM) with screw driver

in direction of arrow, thereby observe LED V21 (figure AL).
Start of stepping mode in direction CLOSE is set correctly if the LED changes
from off to on (see sketch on the left).

Direction OPEN, first stepping mode then normal operation

.

Run valve in direction OPEN to the desired end of stepping mode.

.

Press down

and turn setting spindle K (figure AM) with screw driver

in direction of arrow, thereby observe LED V22 (figure AL).
End of stepping mode is correctly set if the LED changes from on to off (see
sketch on the left).

Direction CLOSE, first stepping mode then normal operation

.

Run valve in direction CLOSE to the desired end of stepping mode.

.

Press down

and turn setting spindle G (figure AM) with screw driver

in direction of arrow, thereby observe LED V21 (figure AL).
End of stepping mode is correctly set if the LED changes from on to off (see
sketch on the left).

50

Multi-turn actuators SA 07.1 – SA 30.1/ SAR 07.1 – SAR 30.1
with actuator controls AUMA MATIC AM 01.1 / AM 02.1

Operation instructions

V 22 off V22 on

normal operation stepping

Start stepping mode OPEN

V 21 on V21 off

stepping normal operation

Start stepping mode CLOSED

Figure AM: Control unit

G

K

V 22 on V22 off

stepping normal operation

End stepping mode OPEN

V 21 off V21 on

normal operation stepping

End stepping mode CLOSED

Advertising