Actuator controls auma matic, Collective fault signal 34,35, Interface board 34 – AUMA Electric multi-turn actuators SA 07.1 - 16.1_SAR 07.1 - 16.1 MATIC AM 01.1 - 02.1 User Manual

Page 34

Advertising
background image

20.

Actuator controls AUMA MATIC

20.1 Functions of the diagnosis LEDs on the interface board (standard version)

V14 is illuminated: Phase failure and/ or motor protection tripped.

In combination with motor protection (PTC thermistor)
(option):
Reset by selector switch position

III

at local controls

V15 is illuminated: Torque fault: Torque switch operated in mid-travel
The LEDs STOP, CLOSE, OPEN indicate the available control commands
(only in selector switch position REMOTE).

34

Multi-turn actuators SA 07.1 – SA 30.1/ SAR 07.1 – SAR 30.1
with actuator controls AUMA MATIC AM 01.1 / AM 02.1

Operation instructions

Figure AA: Positions of the boards within the controls

Timer board
(option)

Cover plate
Interface board

Logic boards

Cover

Positioner board
(option)

Figure AB: Cover plate on interface board

Advertising