20.3 EMERGENCY - OPEN and EMERGENCY - CLOSE signal (option)

(5

th

digit in wiring diagram MSP … C, D, or P)

When an EMERGENCY run command is given, the actuator operates the valve
to the predetermined end position (effective in all three selector switch positions:
LOCAL, OFF, REMOTE).

.

The input at terminal X

K

1 (refer to wiring diagram) must be connected to an

NC contact (closed circuit principle).

.

If EMERGENCY - OPEN or EMERGENCY - CLOSE signal is generally not
desired:
Take off cover plate and disconnect links B1 (for EMERGENCY - CLOSE) and
B2 (for EMERGENCY - OPEN).

36

Multi-turn actuators SA 07.1 – SA 30.1/ SAR 07.1 – SAR 30.1
with actuator controls AUMA MATIC AM 01.1 / AM 02.1

Operation instructions

Figure AD: Cover plate for EMERGENCY - OPEN or EMERGENCY - CLOSE option

Links:B1 (EMERGENCY-CLOSE)

B2 (EMERGENCY-OPEN)