Fuses, 1 fuses within the actuator controls, Fuses 52 – AUMA Electric multi-turn actuators SA 07.1 - 16.1_SAR 07.1 - 16.1 MATIC AM 01.1 - 02.1 User Manual

Page 52

Advertising
background image

23.

Fuses

.

Switch off the mains before changing the fuses.

.

When replacing fuses, only fuses according to table 13 may
be used.

23.1 Fuses within the actuator controls

Fuses (figures AP and AO) are accessible after removal of the local controls.

F1/ F2:

Primary fuses on power supply unit

F3:

Internal 24 V DC supply, RWG, logic board

F4:

Internal 115 V AC supply (optional: 24 V AC);
Heater, tripping device for PTC thermistors,
control of reversing contactors, remote operation

.

After replacing the fuses, screw local controls back on again.

52

Multi-turn actuators SA 07.1 – SA 30.1/ SAR 07.1 – SAR 30.1
with actuator controls AUMA MATIC AM 01.1 / AM 02.1

Operation instructions

Figure AO: Fuses on power supply board

F3

F4

Switchgear

Voltage supply

(mains voltage)

Voltage output

(power supply unit)

G fuses:

(figures

AP

and

AO

)

F 1/F 2

(Board A20, refer to

wiring diagram)

F 3*

)

(Boards A2, refer to

wiring diagram)

F 4*

)

(Boards A8, refer to

wiring diagram)

Reversing
contactors

500 V

24 V

1 A T; 500 V

AUMA article no.:

K002.277

500 mA T; 250 V

1.6 A T; 250 V

115 V

0.4 A T; 250 V

> 500 V

24 V

2 A FF; 660 V

AUMA article no.:

K002.665

1.6 A T; 250 V

115 V

0.4 A T; 250 V

Thyristors

500 V

24 V

16 A FF; 500 V

AUMA article no.:

K001.189

1.6 A T; 250 V

115 V

0.4 A T; 250 V

Size

6.3 x 32 mm

5 x 20 mm

5 x 20 mm

*) according to IEC 60127-2/III

Table 13

Figure AP: Fuses on signal and control board

1F2

1F1