21.3 Positioner adjustment for end position CLOSED (standard version)

Before beginning the setting of the positioner, it has to be
ensured that the limit and torque switching of the actuator as
well as the feedback have been set (clauses 16. and 17.).

.

Set selector switch (local controls) to position LOCAL.

.

Move multi-turn actuator by pressing push button to

end position CLOSED

.

.

Supply nominal value E1 of 0 or 4 mA (see wiring diagram).

.

Turn potentiometer “t-off” (P10) counterclockwise to the stop
(figure AG).

Missing signals E1/ E2 or wrong polarity are indicated by LED
(V10) “E1/E2 < 4 mA" (figures AE or AG)

.

Connect voltmeter to measuring points MP3 and MP4 (figure AG) for measur-
ing the nominal value (0 – 5 V).
For a nominal value E1 of 0 mA, the voltmeter shows 0 V.
For a nominal value E1 of 4 mA, the voltmeter shows 1 V.
In case nominal value (0 V or 1 V) is not correct:
Correct nominal value signal from control room.

.

Connect voltmeter to measuring points MP2 and MP1 for measuring the
actual value signal.
For an actual value E2 of 0 V, the voltmeter shows 0 V.
For an actual value E2 of 5 V, the voltmeter shows 1 V.
If measured value is not correct:
Adjust position feedback according to clause 16. and 17. and repeat
“positioner adjustment”.

41

Multi-turn actuators SA 07.1 – SA 30.1/ SAR 07.1 – SAR 30.1

Operation instructions

with actuator controls AUMA MATIC AM 01.1 / AM 02.1

If

Possible LED display:

(refer to figures AG and AH)

Then

Required setting in end position CLOSED:

(refer to figures AG and AH)

the LEDs are not illuminated

Turn potentiometer “0” (P3) slowly clockwise until
LED

(V27 yellow) is illuminated

LED

(V28 green) is

illuminated

Turn potentiometer “0” (P3) slowly clockwise until
LED

(V28 green) is no longer illuminated and

LED

(V27 yellow) is illuminated

LED

(V27 yellow)

is illuminated

Turn potentiometer “0” (P3) counterclockwise until
LED

(V27 yellow) is no longer illuminated.

Then turn potentiometer “0” (P3) slightly clockwise until
LED

(V27 yellow) is illuminated

Table 8