2 setting actuator behavior on loss of signal, Loss of signal 40 – AUMA Electric multi-turn actuators SA 07.1 - 16.1_SAR 07.1 - 16.1 MATIC AM 01.1 - 02.1 User Manual

Page 40

Advertising
background image

21.2.2 Setting actuator behavior on loss of signal

In case of a loss of signal of nominal value E1 or actual value E2, the reaction of
the actuator can be programmed via the switch S2-7. The complete range of
choices, however, is only available with signals 4 – 20 mA.

The following reactions are possible:

Fail as is:

Actuator stops immediately and remains in this position.

Fail close

Actuator moves the valve to the end position CLOSED.

Fail open:

Actuator moves the valve to the end position OPEN.

40

Multi-turn actuators SA 07.1 – SA 30.1/ SAR 07.1 – SAR 30.1
with actuator controls AUMA MATIC AM 01.1 / AM 02.1

Operation instructions

Behavior on loss of signal of

Prerequisite

1)

Programming

E1

E2

Command signal

Setpoint E1

Feedback

Actual value E2

2)

via DIP switch S2-7

(see figure AF)

fail as is

4 – 20 mA

4 – 20 mA

fail close

4 – 20 mA

4 – 20 mA

0 – 20 mA
0 – 5 V

4 – 20 mA

fail open

4 – 20 mA

4 – 20 mA

4 – 20 mA

0 – 20 mA
0 – 5 V

fail as is

fail open

4 – 20 mA

0 – 5 V

fail close

fail open

4 – 20 mA
0 – 20 mA

0 – 5 V

0 – 20 mA

4 – 20 mA

0 – 20 mA
0 – 5 V
0 – 10 V

0 – 20 mA
0 – 5 V

fail close

fail as is

0 – 20 mA

4 – 20 mA

0 – 10 V

4 – 20 mA

1)

During loss of signal, signals from 0 – 20 mA and 0 – 5 V may be misinterpreted since E1 or E2 (without any fault) can also
be < 4 mA (end position CLOSED = 0 mA or 0 V) when working properly.

2)

Signals for internal feedback:
0/4 – 20 mA from electronic position transmitter or 0 – 5 V from precision potentiometer 5 k

Ω

Table 7: Possible settings

Advertising