21.8 Positioner in Split Range version (option)

For Split Range, a modified version of the positioner is used. The standard ver-
sion is not suitable for Split Range operation.
Split Range operation is only possible with the position transmitter RWG.

21.8.1 Split Range: description of functions

In Split Range operation, a setpoint is shared by up to four positioners. A typical
example is a pipeline with a bypass. The actuator mounted on the bypass reacts
in the lower range (0 – 10 mA), the actuator on the main valve in the upper
range (10 – 20 mA). Other values such as 4 – 12 mA and 12 – 20 mA can also
be set.

21.8.2 Programming

DIP 5 at code switch S1-7 must always be in position ON for Split Range ver-
sion.

The further programming of the positioner via the code switch S2-7 can be
made in the same way as during normal operation.

21.8.3 Positioner adjustment for Split Range

(see also example further down the page)

.

Supply the specified minimum command signal (nominal value E1) for the
positioner and check by measuring with voltmeter at the measuring points MP3
and MP4 (figure AK).

.

Connect voltmeter between measuring point M3 and measuring point MP1.
Calculate setting value:
Initial value = E 1

min

[in Ampere] x 250 Ohm

Set initial value with potentiometer P5.

.

Supply specified maximum command signal (nominal value E1) and check by
measuring at the measuring points MP3 and MP4.

.

Connect voltmeter between measuring point M9 and measuring point MP1.
Set potentiometer P6 to 5 V.

.

Supply input signal E1 from minimum to maximum value and check the set
range 0 – 5 V at measuring point M9. If necessary, readjust with P5 or P6.

.

Apply the same procedure to the second actuator’s positioner and set accord-
ing to the specified nominal values E1.

.

After setting the Split Range operation, perform further readjustment as
described on page 41.

47

Multi-turn actuators SA 07.1 – SA 30.1/ SAR 07.1 – SAR 30.1

Operation instructions

with actuator controls AUMA MATIC AM 01.1 / AM 02.1

Programming

Command signal

Setpoint E1

Feedback

1)

Actual value E2

via DIP switch S1-7

(see figure AK)

4 – 12/12 – 20 mA
0 – 10/10 – 20 mA

4 – 20 mA
0 – 20 mA

4 – 12/12 – 20 mA
0 – 10/10 – 20 mA

0 – 5 V

1)

Signals for internal feedback:
0/4 – 20 mA from electronic position transmitter

Table 12: Possible settings for Split Range operation