Operation and indications of the local controls – AUMA Electric multi-turn actuators SA 07.1 - 16.1_SAR 07.1 - 16.1 MATIC AM 01.1 - 02.1 User Manual

Page 20

Advertising
background image

10.

Operation and indications of the local controls

Selector switch

Position OFF (0):

- No remote control possible
- No local control possible
- Actuator remains ready for signalization

signalization (the controls’ power supply is maintained)

Position Local control (I):

The actuator can be operated locally via the push buttons

OPEN - STOP - CLOSE.

Position Remote control (II):

The actuator can be controlled from remote, e.g. via the con-
trol room.

Position Test (III):

Test PTC tripping device (refer to page 27)
Only available in combination with motor protection
(PTC thermistor).
Yellow indication light (fault) is illuminated.

Position Reset (III):

Reset fault signal (yellow indication light) after the motor pro-
tection has tripped (refer to page 54).
Only available in combination with motor protection
(PTC thermistor).

20

Multi-turn actuators SA 07.1 – SA 30.1/ SAR 07.1 – SAR 30.1
with actuator controls AUMA MATIC AM 01.1 / AM 02.1

Operation instructions

Figure M: Local controls

Selector switch

Push buttons

Indication lights

I

I

0

I

I

0

I

I

0

Reset

III

Test

III

I

II

0

Test

III

Reset

I

II

III

0

Advertising