Cross sections 18, Protective earth 18 – AUMA Electric multi-turn actuators SA 07.1 - 16.1_SAR 07.1 - 16.1 MATIC AM 01.1 - 02.1 User Manual

Page 18

Advertising
background image

Connecting the cables

.

Connect cables according to order-related wiring diagram.
Cross sections:
- Power terminals (U1, V1, W1, U2, V2, W2) and

protective earth (symbol:

)

max. 6 mm² flexible, max. 10 mm² solid

- Control contacts (1 to 50) = max. 2.5 mm²

.

All PE conductors have to be tightened firmly to the PE connection
(symbol:

) using either ring lugs (flexible cables), or lugs (solid cables) (fig-

ure H).

Each time the PE connection has been disconnected, it has to
be ensured that the PE conductors are firmly connected.

Screw

Washer

Circlip

Protective earth with ring lugs/lugs

PE connection

Socket carrier

Closing the terminal compartment

.

Insert socket carrier into the cover and fasten with screws (2) (figure G).

.

Clean sealing faces at the cover and the housing.

.

Check whether O-ring is in good condition.

.

Apply a thin film of non-acidic grease (e.g. Vaseline) to the sealing faces.

.

Replace cover and fasten bolts (1) evenly crosswise.

.

Fasten cable glands with the specified torque to ensure the required enclo-
sure protection.

Parking frame, protection cover (accessories)

A special parking frame (figure J) for protection against touching the exposed
contacts and against environmental influences is available.
The open terminal compartment can be closed using a protective cover
(not illustrated).

Multi-turn actuators SA 07.1 – SA 30.1/ SAR 07.1 – SAR 30.1
with actuator controls AUMA MATIC AM 01.1 / AM 02.1

Operation instructions

18

Figure J: Parking frame (accessory)

Parking frame

Figure H: PE connection