17.2 Setting 3- / 4- wire system 4 – 20 mA

.

Connect voltage to electronic position transmitter via AM.

.

Move valve to

end position CLOSED

.

.

Connect ammeter for 0 – 20 mA to measuring points (figure Y-2).

The circuit (external load) must be connected
(observe max. load R

B

), or the appropriate poles at the terminals

(refer to wiring diagram) must be linked, otherwise no value can
be measured.

.

Turn potentiometer (E2) clockwise to the stop.

.

Turn potentiometer (E2) back a little.

.

Turn potentiometer “0” clockwise until output current starts to increase.

.

Turn back potentiometer “0” until a residual current of approx. 0.1 mA is
reached.

.

Move valve to end position OPEN.

.

Set potentiometer “max.” to end value 16 mA.

.

Move valve to end position CLOSED.

.

Set potentiometer “0” from 0.1 mA to initial value 4 mA.
This results in a simultaneous shift of the end value by 4 mA, so that the range
is now 4 – 20 mA.

.

Approach both end positions again and check setting. If necessary, correct the
setting.

If the maximum value cannot be reached, the selection of the
reduction gearing must be checked.

32

Multi-turn actuators SA 07.1 – SA 30.1/ SAR 07.1 – SAR 30.1
with actuator controls AUMA MATIC AM 01.1 / AM 02.1

Operation instructions

Figure Y-2

“0” (0/4 mA)

“max.” (20 mA)

Meas. point (+)
0/4 – 20 mA

Meas. point (–)
0/4 – 20 mA

Cover plate

E2