Commissioning english – Burkert Type 8645 User Manual

Page 126

Advertising
background image

126 - 8645

CommissioninG

English

Examples for hardware configuration and explanation of the different module types

Illustration: Example of maximum configuration with 16 IN / 16 OUT

Pull the main/inside module DI16/DO16 into the slave, Type 8645/MK01 (drag and drop).

Combination module

4PO / 4DI

Type 8645 / MK01

Combination module

4PO / 4DI

Combination module

4PO / 4DI

Combination module

4PO / 4DI

Termination module

Illustration: Example of maximum configuration with 16 IN / 16 OUT (with combination modules 4PO/4DI)

Module types
Main/Inside DI16/DO16

Main module/intermediate module: 2 byte inputs , 2 byte outputs

Main/Inside DI8/DO8

Main module/intermediate module: 1 byte inputs , 1 byte outputs

Main/Inside only DI8

Main module/intermediate module: 1 byte inputs

Main/Inside only DO8

Main module/intermediate module: 1 byte outputs

Add-on DI8

Expansion module: 1 byte inputs

Add-on DO8

Expansion module: 1 byte outputs

A main inside module must be used for each hardware configuration. Empty slots upt to 2 buytes IN or 2 bytes
OUT can be filled with the add-on modules.
In the above example, a 2 byte IN / 2 byte OUT module was used. The inputs occupy the EB 1 and 2, the
outputs the AB  and 4.