ConfiGuraTion anD funCTion of The moDules

English

8645 - 51

Object 100c hex - Guard time

Guard time - Value in ms

Guard time multiplied by the life time factor gives the life time for the guarding protocol.
The value ”0“ means that the object is not used.

Length:

16 Bit

Default value:

500 ms

Object 100d hex - Life time factor

Life time factor – value
Description, see object 100C hex guard time.

Length:

8 Bit

Default value:



Object 1014 hex - cOB-Id Emerg�ency

Defines the COB – ID of the emergency object.

Length:

2 Bit

Default value:

[80 hex + Address]

Object 1015 hex - Inhibit Time EMcy

Inhibit Time EMCY - value in 0.1 ms
This value allows the inhibit time for emergency telegrams to be set.

The value ”0“ means that the objects is not used.

Length:

16 Bit

Default value:

0 hex

Object 1016 hex - consumer heartbeat Time

Up to three heartbeat producers can be monitored with the CANopen module.

Sub index

content

Default

Length

Access

read

write

00 hex

Number of object entries



8 Bit

X

-

01 hex

Consumer heartbeat time 1

0

2 Bit

X

X

02 hex

Consumer heartbeat time 2

0

2 Bit

X

X

0 hex

Consumer heartbeat time 

0

2 Bit

X

X

Structure of heartbeat time:

bits 31 to 24

bits 23 to 16

bits 15 to 0

Reserved (value 0x00)

Node-ID

Heartbeat time (ms)

Object 1017 hex - Producer heartbeat Time

The producer heartbeat time defines the cycle time of the heartbeat telegram in ms.

Length:

16 Bit

Default value:

0 ms