Commissioning english – Burkert Type 8645 User Manual

Page 151

Advertising
background image

CommissioninG

English

8645 - 151

Illustration: Overview of the device parameter settings

The parameters are explained in this table:

ID

parameter

Explanation

1

Produce Size Poll

Number of bytes of input data (in the desired module list)

2

Consume Size Poll

Number of bytes of output data (in the desired module list)



Output Diagnosis

The output diagnosis (output short-circuit report or attempt
to control a non-existent output) can be activated or de-ac-
tivated with this parameter.

4

Input Filter

The input filter (only signals > 4 ms are recognized) can be
activated or de-activated using this parameter.

5 to 19

Configured Module #1 to #15

A list of all modules present stored in the desired module list
in EEPROM.

20 to 4

Actual Module #1 to #15

A list of all modules in the actual module list that were reco-
gnized during start-up by the hub.

5 to 50

Output Value Word #0 to #15

The outputs can be manually adjusted with this parameter.

51 to 82

Error Action #0 to #15

Determines the reaction of the outputs if a bus error
occurs.
0: Output uses the error value.
1: Output keeps its current setting.

Error Value #0 to #15

Determines the condition of the outputs if a bus error oc-
curs.

NOTE!

Changes to ID , 4 and 51 to 82 are only permanently accepted into EEPROM if the
value  is written on Object Class 150 Instance 1 Attribute 5. Otherwise the changes are
lost after a reset.