ConfiGuraTion anD funCTion of The moDules

English

Further description the Fieldbus Node cANopen

The valve island corresponds to the ”Pre-defined device“ according to CANopen – standard V4.10. The ”De-
vice Profile 401 (I/O – Modules) V1.4“ applies to the functions and objects.

NOTE!

The terms ”address“ (abbreviated ”Adr.“) and node ID have the same meaning in this
description.

Identifier

The following IDs are used.

Object

Identfier

NMT

0 hex

SYNC

80 hex

EMERGENCY

80 hex + Address

1st TPDO

180 hex + Address

1st RPDO

200 hex + Address

2nd TPDO

280 hex + Address

2nd RPDO

00 hex + Address

rd TPDO

80 hex + Address

rd RPDO

400 hex + Address

4th TPDO

480 hex + Address

4th RPDO

500 hex + Address

TSDO

580 hex + Address

RSDO

600 hex + Address

GUARDING

700 hex + Address