Multipole module, Configuration and function, Technical data – Burkert Type 8645 User Manual

Page 75: General technical data, Config�uration and function, Configuration and function of the modules english

Advertising
background image

ConfiGuraTion anD funCTion of The moDules

English

8645 - 75

MuLTIPOLE MOduLE

config�uration and Function

The multipole module brings a bundle of individual core pairs
together to form a multi-core cable that enables the signal to
pass from the higher-level controller to the FreeLINE automation
system.

Illustration: Multipole module

Technical data

General Technical data

Operating voltage

24 V -15 % / +20 %

Residual ripple

2 Vss

Electrical connections

M2
jack, leads for inputs
plug, leads for outputs / valves

Pneumatic connections
Compressed air supply

Exhaust air
Auxiliary control air
Pilot control exhaust air


G 1/4”, NPT 1/4”, D10
G 1/4”, NPT 1/4”, D10
M5, D6, D4, D 1/4”
M5, D6, D4, D 1/4”

Material

PBT

Weight

485 g

cAuTION!

The multipole module itself does not have any protection against SURGE pulses.

As the multipole module is controlled via the inputs and outputs of a PLC, care must be
taken that a corresponding protection device is provided further upline (e.g. at the PLC).

NOTE!

If the multipole module is used on conjunction with feedback inputs, we recommend the
installation of a filter (> 4 ms) in the higher-level control unit (e.g. PLC). Otherwise incorrect
messages may be transmitted when using M8 plugs (without plastic insert) due to ESD.

Advertising